Resolution Direct Vent Gas Fireplace
72” Minimum
Ceiling
12” Max.
Depth
2
1
/
2
” Max Depth
10” min.
From Opening
16” Min.
From Opening
6” Min.
FP2595
mantel clearances
Hearth
8” Min.
Noncombustible
Hearth Minimum
Fireplace Opening
cLeaRances
cLeaRances tO cOMBustIBLes
ManteL cLeaRances
nOte: the combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
w
a
R
n
In
G
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring,
the appliance shall be installed on a metal, wood or noncombustible
material panel extending full width and depth of the appliance.
FP2128
12"
16"
10"
12"
6"
2
1
/
2
"
FP2204
mantel clearances
Wall
Stud
Insulation
Board
Standoff
Top of Fireplace
Opening
FP2235
side View
Figure 4 -
Clearances from the mantel, ceiling, and side wall.
6"
5"
3"
2
1
/
2
"
4
1
/
2
"
45°
1"
3
1
/
2
"
FP2129
mantel leg
1
1
/
2
"
FP2129
Fireplace Opening
Figure 5 -
Mantel clearances
top View