background image

9

Vermont Castings Madison

To meet these requirements, a floor protector must

be at least 54” (1372mm) wide (“A”,Fig. 12) and 52”
(1320mm) deep (“B”, Fig. 12).

Fireplace Hearth Protection

Do not assume that your fireplace hearth is completely
noncombustible. Many fireplace hearths do not satisfy
the “completely noncombustible” requirement because
the brick or concrete in front of the fireplace opening is
supported by heavy wood framing. (Fig. 13)  Because
heat is readily conducted by brick or concrete, it can
easily pass through to the wood.  As a result, such
fireplace hearths can be a fire hazard and are consid-
ered a combustible floor.

For all fireplace installations, follow the floor

protection guidelines described above.

Keep in mind that many raised hearths will extend

less than the required clearance from the front of the
heater when it is installed.  In such cases, sufficient
floor protection as described above must be added in
front of the hearth to satisfy the minimum floor protec-
tor requirement from the front of the stove:  18" (460
mm) from the front in the United States and 18" (460
mm) from the front in Canada.

Hearth rugs do not satisfy the requirements for

floor protection as they are only fire-retardant, not fire
proof.

Fig. 13   Supporting timbers under fireplace hearths are
considered to be combustible.

Wood framing
requires protection
from radiant heat

ST247a

Clearance to Surrounding

Combustible Materials

When the stove is operating, both the stoveplate and
the chimney connector radiate heat in all directions.  A
safe installation requires that adequate clearance  be
maintained between the stove and nearby combustible
materials to ensure that those materials do not
overheat.

Clearance is the distance between either your

stove or chimney connector, and nearby walls, floors,
the ceiling, and any other fixed combustible surface.
Keep  furnishings and other combustible materials
away from the stove as well.
  In general, a distance
of 48" (1220 mm) must be maintained between the
stove and moveable combustible items such as drying
clothes, furniture, newspapers, firewood, etc.  Keep
this area empty of any combustible material.

Safe Ways To Reduce Clearances

The Madison clearance requirements, listed and
diagramed on pages 12-13, have been established
through testing to UL and ULC standards to meet most
installation configurations. These involve four basic
variables:

• 

When neither the 

chimney connector nor the wall

has a heat shield  installed.

• 

When only the 

chimney connector has a heat

shield installed.

• 

When only the 

wall has a heat shield  mounted on it.

• 

When a heat shield is installed on 

both the

chimney connector and wall.

In general, the greatest clearance is required when

the stove will be positioned with no heat shield near a
wall with no heat shield.  The least clearance is re-
quired when both the stove and the wall have heat
shields.  Reducing a stove clearance may require
installation of a listed heat shield on the chimney
connector as well.

Clearances may be reduced only by means

approved by the regulatory authority, or in accordance
with the clearances listed in this manual.

D

A

B

A

D

C

C

E

C

E

C

Top Vent

Rear Vent

F

Fig. 12   These dimensions are minimum requirements only.
Use greater dimensions whenever possible.

Floor Protection Requirements

A:

48”

54”

(1372mm)

B:

48”

52”

(1321mm)

C:

4”

8”

(203mm)

D:

18”

18”

(460mm)

E:

16”

18”

(460mm)

F:

10”

10”

(254mm)

U. S.

Canada

ST500a

Summary of Contents for Madison 1655

Page 1: ...RE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH CONTACT LOCAL BUILDING OFFICIALS...

Page 2: ...n Agency 40 CFR Part 60 532 b 2 as stated on the permanent label attached to each stove The Madison Model 1655 Series meets Washington State requirements We recommend that you hire a professional soli...

Page 3: ...e content of the fuel used as well as the design construction and climatic location of your home Figures shown are based on maximum fuel consumption obtained under laboratory conditions and on average...

Page 4: ...The metal label permanently attached to the back of the stove indicates that the Madison has been tested to current UL and ULC standards by CSA Clearance and installation information is also printed...

Page 5: ...connection from the stove to the chimney They are for interior use only Double wall connectors must be tested and listed for use with solid fuel burning appliances Single wall connectors should be mad...

Page 6: ...nnector sections Securing the Single wall Connector to a Prefabricated Chimney Follow the installation instructions of the chimney manufacturer exactly Special adaptors are available from your local d...

Page 7: ...been tested and listed for use as a wall pass through U S Requirements The National Fire Protection Association NFPA has established guidelines for use in the United States for passing chimney connect...

Page 8: ...rom left side E Fig 9 Wall Pass through using single wall chimney connector with a ventilated steel thimble Min 6 152mm Chimney clearance to sheet steel supports and combustibles 2 51mm Min Glass Fibe...

Page 9: ...ned between the stove and nearby combustible materials to ensure that those materials do not overheat Clearance is the distance between either your stove or chimney connector and nearby walls floors t...

Page 10: ...hields Fig 16 Reduced clearances for both rear and side walls Wall shields may meet at corner if desired Shielding for connector is centered behind connector Wall pass through must comply with codes C...

Page 11: ...o Durock or equivalent alcove lining I N T R E P I D I I Metal Stud Combustible facing may overlap metal studs by only 1 1 air gap top and bottom on both sides and back wall 7 16 Durock or equivalent...

Page 12: ...at shields Top exit heat shields on stove no shields on single wall connector Top exit heat shield on stove heat shield on single wall connector Top exit heat shield on stove double wall chimney conne...

Page 13: ...t Installations no heat shields Top Exit Installations heat shield on stove no shields on single wall connector Top Exit Installations heat shield on stove heat shields on single wall connector Top Ex...

Page 14: ...to Wall Stove in Corner PROTECTED SURFACES Madison 1655 Series Clearance Diagram UNPROTECTED SURFACES Rear Exit Installations Bottom Heat Shield floor protection minimum 18 457mm in front Y Z AA BB E...

Page 15: ...lers Leg Bolt and Washer Leg Leveller ST466 Install the Bottom Heat Shield The 1892 Bottom Heat Shield must be used in the U S and Canada in any installation on a floor that is not comprised of unpain...

Page 16: ...two sheet metal screws provided in the kit to attach the Adaptor to the Rear Heat Shield at the aligned holes Without Rear Heat Shield 1 Facing the rear of the stove loosen the pan head screw located...

Page 17: ...s Second ary Air enters the stove through two unrestricted inlets and is heated while passing through separate channels before being delivered through three stainless steel multi ported tubes located...

Page 18: ...vary your firing technique to get the results you desire Starting and Maintaining a Fire Conditioning Your Stove Cast iron is extremely strong but it can be broken with a sharp blow from a hammer or f...

Page 19: ...on for several minutes after refueling Reset the primary air control for the desired heat output after the fire is re established Ash Disposal Remove ash before it reaches the top of the ash pan Check...

Page 20: ...s on the inner gasket with the coated side down marked This Side Out toward the outside of the door Tighten the screws snugly but loose enough to allow for a little move ment of the glass when the sto...

Page 21: ...ney connector should be cleaned by disconnecting the sections taking them outside and removing any deposits with a stiff wire brush Reinstall the connector sections after cleaning being sure to secure...

Page 22: ...gh flue temperatures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney Although steel chimneys are not as attractive as their masonry...

Page 23: ...te is volatile and can generate chimney fire All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize creosote accum...

Page 24: ...tem Description Part Number 1 Bottom Outer 30000795 2 End Left See Chart Pg 25 3 Back 30000798 4 Secondary Manifold Left 30000802 5 Front See Chart Pg 25 6 Load Door See Chart Pg 25 7 Ashlip See Chart...

Page 25: ...Gr 5 Blk 1201337 12 Washer Flat 1 4 Z 1202474 Fallaway Handle Complete 0004342 14 Handle Ceramic 1600620 15 Oval Head Slotted Screw 1 4 20 x 3 375 1201294 16 Griddle Opener Insert Door Handle 1600650...

Page 26: ...26 Vermont Castings Madison...

Page 27: ...cts Company warrants that your Madison will be free of defects in material and workmanship for a period of three years from the date you receive it except that the handles glass door panel fireback ar...

Page 28: ...28 Vermont Castings Madison Vermont Castings Majestic Products 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7885 www vermontcastings com Vermont Castings Majestic Products...

Reviews: