Ceiling Mounted Occupancy Sensors

Installer’s Specifications

Input Voltage 

24 VDC

Current Consumption @ 24 VDC:

   PIR 

21 mA nominal

   Ultrasonic 

34 mA nominal

   Dual 

37 mA nominal

Isolated Relay 

Contact rating: 1A @ 24 VDC resistive

Operating Temperature Range 

0° to 50°C (32° to 122°F)

Operating Humidity Range 

Max. 90%  RH non-condensing

Agency Approvals 

UL and cUL listed; FCC part 15 for home and office use (Class B)

MSC SerieS

MSC SerieS

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.
•  Read and understand the instructions before installing
  this product.
•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

PRODUCT IDENTIFICATION

MSCD2000D

MSCP1000

MSCU2000

Sensing Technology

U = Ultrasonic
D = Dual (PIR + Ultrasonic)
P=  Passive Infrared (PIR)

MSC   

Coverage

1000 = 1000 Sq. Ft. (Passive Infared only)
2000 = 2000 Sq. Ft. (Ultrasonic or Dual technology only)

COVERAGE PATTERNS

For a 9 ft. ceiling

Minor Motion
Major Motion

25 ft

(7.7m)

32 ft

(9.8m)

48 ft

(14.7m)

30 ft

(9.2m)

24 ft

(7.4m)

42 ft

(12.8m)

Minor Motion
Major Motion

Ultrasonic Major Motion
Ultrasonic Minor Motion
PIR Major Motion
PIR Minor Motion

PIR

Ultrasonic

Dual Technology

OPERATION

MSC ceiling-mounted occupancy sensors are ideal for use in business and office 
environments to accurately detect occupancy and automatically control lighting. The 
ceiling-mount design allows the greatest possible motion sensitivity. An adjustment 
panel is on the front of the sensor provides easy access to controls after the sensor is 
installed. 

COVERAGE FEATURES

Model

MSCP1000

MSCU2000

MSCD2000

Technology

PIR

Ultrasonic

Dual

Coverage area

1000 sq. ft.

2000 sq. ft.

2000 sq. ft.

Field of view

360°

Ambient light level sensing

0.5 to 250 foot candles

Adjustable time delay

15 sec. to 30 min.

Adjustable sensitivity

600 to 1000 sq. ft. 

(60% to 100% of 

max. coverage

200 to 2000 sq. ft. 

(10% to 100% of 

max. coverage)

200 to 2000 sq. ft. 

(10% to 100% of 

max. coverage)

Isolated relay

Form C contacts for Class 2 signaling

LED motion indicators

1 (red)

1 (red)

2 (red/green)

Reviews: