background image

Z207871-0A 

Page 1 of 2 

©2019 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0819 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

TM

Installation Guide

Accessories

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

Product Overview

The AG04 carbon monoxide (CO) and nitrogen dioxide (NO

2

) sensing element is designed to work with the Veris 

GWNP Series (BACnet/Modbus Output) gas platform unit to provide accurate monitoring of CO and NO

2

 levels. 

Common sources of CO include automobile exhaust from gasoline engines, gasoline powered furnaces, gasoline 
powered water heaters, and gasoline generators. Common sources of NO

2

 include automobile exhaust from diesel 

engines and diesel powered generators. The sensor is calibrated at the factory, so no field calibration is needed. The 
AG04 is warranted to meet accuracy specifications for two years after the date of manufacture.

AG04

Combination Carbon Monoxide and 

Nitrogen Dioxide Sensing Element

Specifications

Sensor Type

CO:  Electrochemical

NO2:  Electrochemical

 Measurement Range

CO:  0 to 500 ppm

NO2:  0 to 20 ppm

   Accuracy

CO:  ±5% of range

NO2:  ±5% of range

   Resolution

CO:  1 ppm

NO2:  0.1 ppm

Sensor Warranty

2 years from manufacture date

Low Level Setpoint

CO:  25 ppm (default)

NO2:  1 ppm (default)

High Level Setpoint

CO:  180 ppm (default)

NO2:  3 ppm (default)

   Operating Temperature Range

-20 to 40 °C (-4 to 104 °F) 

Operating Humidity Range

0 to 90% RH non-condensing

Note: TheAG04 sensor works only with Veris GWNP (protocol output) Series gas platform devices. The AG04 will not work with 

GWNM, GWNV or GWN1 versions of the GWN Series.

Reviews: