WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT 

MAINTENANCE AND REPAIR. 

BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN 

OBJECTS (E.G. FOIL, PAPER).

the fan is suitable both for horizontal and vertical installation. to get the best performance of the unit and to minimize turbulence-
induced air pressure losses, connect the straight air duct section to the spigots on both sides of the unit while installing. Minimum 
straight air duct length: equal to 1 air duct diameter on intake side and to 3 air duct diameters on outlet side. no filters or any other similar 
devices are allowed to be installed in these sections. 

Model

Dimensions, 

mm

Model

Dimensions, 

mm

H1

H2

H1

H2

VKP 80 mini

60

200

VKP 100/100х4 mini

60

200

H1

H2

VKP 80 Р mini

VKP 100/100х5 mini

VKP 80/80х2 mini

VKP 100/100х6 mini

VKP 80/80х4 mini

VKP 100

VKP 80/80х5 mini

VKP 125

VKP 80/80х6 mini

VKP 125/100x4

VKP 100 mini

VKP 150

250

VKP 100 Р mini

VKP 150/125x2

VKP 100/80х2 mini

VKP 160

VKP 100/80х4 mini

VKP 125 (S) mini (Duo)

200

VKP 100/80х5 mini

VKP 150 mini (Duo)

250

VKP 100/80х6 mini

VKP 200 mini (Duo)

VKP 100/100х2 mini

CAUTION! 

If necessary, close the fan spigot with a plug, lubricate the rubber seal of the spigot with silicone grease.
Silicone grease for rubber seals is purchased separately, plugs are available on request. 

!

Install a backdraft damper to prevent air back drafting (optionally).

a) Unit ceiling mounting

b) Unit wall mounting

INSTALLATION AND SET-UP

Summary of Contents for VKP 125 mini

Page 1: ...VKP mini Inline centrifugal fan USER S MANUAL...

Page 2: ...nstallation certificate 19 Warranty card 19 This user s manual is a main operating document intended for technical maintenance and operating staff The manual contains information about purpose technic...

Page 3: ...unit and any unauthorised modifications are not allowed Do not expose the unit to adverse atmospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky sub...

Page 4: ...amaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a safety hazard Ensure that the unit is switched off from the supply mains before remo...

Page 5: ...d space for mounting The unit is rated for continuous operation The unit is a component part and is not designed for stand alone operation Transported air must not contain any flammable or explosive m...

Page 6: ...33 2 26 0 34 138 1800 36 3 45 0 4 176 2600 44 VKP 100 mini 1 230 20 0 32 97 1400 33 2 26 0 34 138 1800 36 3 45 0 4 176 2600 44 VKP 100 80 2 mini 1 230 20 0 32 97 1400 33 2 26 0 34 138 1800 36 3 45 0...

Page 7: ...176 2600 44 VKP 100 1 230 50 58 0 26 240 2500 47 50 VKP 125 1 230 50 58 0 26 340 2500 48 VKP 125 100 2 1 230 50 58 0 26 340 2500 48 VKP 125 100 4 1 230 50 58 0 26 340 2500 48 VKP 150 VKP 160 1 230 50...

Page 8: ...149 149 340 207 447 350 7 7 VKP 200 mini 198 198 362 222 494 397 8 8 VKP 200 mini Duo 198 198 362 222 494 397 8 8 VKP 100 99 99 252 133 420 321 4 5 VKP 125 124 124 252 133 420 321 4 5 VKP 150 149 149...

Page 9: ...100 100 4 mini 99 99 252 110 166 297 253 3 4 VKP 125 100 4 124 99 252 133 191 370 321 5 0 VKP 80 80 5 mini 79 79 252 90 136 351 253 3 5 VKP 100 80 5 mini 99 79 252 110 166 351 253 3 7 VKP 100 100 5 m...

Page 10: ...ting capacitor and a terminal block inside and is attached to the casing end face The flange with the turbine and the fixing bracket with mounting slots are screwed to the back or front panel of the f...

Page 11: ...to be installed in these sections Model Dimensions mm Model Dimensions mm H1 H2 H1 H2 VKP 80 mini 60 200 VKP 100 100 4 mini 60 200 H1 H2 VKP 80 mini VKP 100 100 5 mini VKP 80 80 2 mini VKP 100 100 6...

Page 12: ...ll the holes and fix the bracket with matching fasteners e g dowels see Fig b Install the fan on the fixing bracket Fig c Tighten the fixing screws Fig d Connect the air ducts to the fan spigots Fig e...

Page 13: ...d VKP mini Duo low speed VKP mini Duo medium speed DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A...

Page 14: ...impellers The screw connection is loose Check the screw connection and tighten the screws if needed TECHNICAL MAINTENANCE TROUBLESHOOTING DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE O...

Page 15: ...ling unit setup To benefit from warranty repair the user must provide the unit the user s manual with the purchase date stamp and the payment paperwork certifying the purchase The unit model must comp...

Page 16: ...VKP mini 16 www ventilation system com...

Page 17: ...17 www ventilation system com...

Page 18: ...VKP mini 18 www ventilation system com...

Page 19: ...TE The _____________________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Techni...

Page 20: ...V17EN 06...

Reviews: