5.2 Error schemes
5.2.1 General error
The unit no longer works properly or the
error is not indicated in the table.
Reset the unit by pulling out the plug during 10 seconds
and then place it back again
Wait 15 minutes.
Does do unit work again?
Yes
No
Open the front cover using the clip
locks and open the control unit
Is there 230V on the
phase of the control
unit
Yes
No
Replace the
control unit and
place the plug
back in the socket
The error is (tempo-
rarily) fixed, pay
attention to whether
new errors occur
Pull the plug out
of the socket
Pull the plug out
of the socket
Replace the fuse
at the control unit
Put the plug back
into the socket
If the fuse breaks
again, pull the plug
out of the socket
and check all
internal wiring
Put the plug back
in the socket
Replace the
damaged wiring
This
scheme
is
meant
for
the
installer only.
Maintenance
performed
by the end user is not only
dangerous, but also has
disadvantageous
conse-
quences for the warranty.