19
B A
G
POWER
ETH_Link
Modbus
RESET
G0
FACT
RESET
100Mbps
5.4
C
ONVERTER CONNECTION
Enter the IP address of the device, the default values are:
•
IP:
192.168.0.50
•
Address mask IP: 255.255.255.0
•
TCP Port: 80
•
Modbus: ASCII, 9600 baud, 8 bit data, 1 bit stop, No parity, address 1, delay 30
5.5
C
ONVERTER SETTINGS
After entering the converter's IP address, the login screen should appear in the browser. Enter your
login and password there and click "Login". The default account is:
•
Login:
admin
•
Password:
admin
After logging in, select the option
Detail
at the bottom right of the screen.
In the subpage
Ethernet
Configuration
, you must replace the factory IP with your own and set the
network settings.
In the subpage
Modbus
Configuration
, the communication parameters of the converter with the
UCS controller must be set. The communication parameters must be identical to those set on the
UCS controller.
For the ERC20 and CU24V1 controllers, you can find the communication parameters in the RMC20
panel menu.
For UCS controllers, the parameters can be found in the controller menu.
After entering new data, the converter is reset automatically and you must enter the new IP into the
browser to connect to the converter.