Velocity VDOT-STB-SCI Instruction Manual Download Page 1

GLT-299-7-8  Rev.  0 

Mar  23,  2018 

 
Instruction Manual 

VDOT-STB-SCI   
Short Circuit Isolator Base 

 

Before Installation 

Please read these instructions carefully and keep for future reference.   

The information in this document is subject to change without notice. For updates please refer to our website.

   

 

Do not use the products outside the rated power supply voltage range specified in 
the Specifications. It may cause a fire or damage to equipment.

  !   CAUTION  

 

Do not disassemble, repair, or modify the products. It may cause a fire or electric 
shock.

  !   CAUTION  

 

Make  sure  to  turn  the  power  off  before  commencing  any  wiring  work.  Otherwise  it 
may cause electric shock or damage to equipment.

  !   CAUTION  

 

Note: 

Follow the requirements for the installation of the products in accordance with the Specifications. Otherwise 

it may cause damage to equipment. 

Note:

 Do not install the product in any location where oil, dust, iron powder, chemicals, or hydrogen sulphide may 

occur or affect the product. It may cause damage to equipment.

   

 

Section 1 – INTRODUCTION 

VDOT-STB-SCI is a detector base with short circuit isolator for use with Zeta Control Panel series, which does 

not  require  an  address.  The  detector  base  isolates  short-circuit  to  protect  detectors  from  failing.  When 

short-circuit is detected LED indicator illuminates, and short-circuited area is isolated automatically. Upon removal 

of the short condition, the area is automatically connected to go back to the normal standby status. 

 

Section 2 – TERMINALS

 

VDOT-STB-SCI base is supplied with 3 terminals as standard. The terminals of VDOT-STB-SCI base head are 

configured as follows: 

 

-

Terminal 1 = SLC positive 

-

Terminal 6 = SLC negative IN 

-

Terminal 5 = SLC negative OUT 

 

 

ZETA ALARMS LIMITED 

72-78 MORFA ROAD, SWANSEA, SA1 2EN 

  http://www.velocitydetection.com 

Summary of Contents for VDOT-STB-SCI

Page 1: ...ns Otherwise it may cause damage to equipment Note Do not install the product in any location where oil dust iron powder chemicals or hydrogen sulphide may occur or affect the product It may cause dam...

Page 2: ...GLT 299 7 8 Rev 0 Mar 23 2018 2 5 6 1 SCI indicator Figure 1 Position of terminals Section 3 DIMENSIONS Figure 2 Dimension of VDOT STB SCI mm inch 105 4 133 22 5 0 885...

Page 3: ...9 7 5 Optional accessory VDOT ADP adapter Use this adapter when VDOT STB SCI is installed with a 4 square electrical box or 4 octagonal electrical box Refer to VDOT ADP Instruction Manual for details...

Page 4: ...ure 5 Connection to terminals For system monitoring for terminals 1 5 and 6 do not use looped wire under terminals Break wire run to provide monitoring of connections CAUTION Before installing the pro...

Page 5: ...n has been evaluated and found suitable for that purpose Section 7 MAINTENANCE Maintenance The VDOT STB SCI is a high quality product engineered for reliability In order to obtain optimum performance...

Page 6: ...nt Consumption Standby 100 A Activated SCI Isolation 22mA SLC Line impedance Up to 50ohms 2km 1 24mile Refer to below SCI On Resistance 0 2ohms max SCI Fault Detection Voltage 10V min Visual Indicator...

Page 7: ...stion or b at the Zeta s option repayment of the price where this had been paid And the warranty period is three 3 years from the shipment from Zeta s factory 1 3 Notwithstanding anything to the contr...