VELIT 2000U Instruction Manual Download Page 20

 

20 | 

Page

 

6.TROUBLESHOOTING 

6.1 Error code 

There are multiple sensors built inside the unit. When an error is detected, the error icon 
will flash with the error code displayed. Check the table below for the meaning of the error 
codes and contact customer service when needed. 
 

Code

 

Cause

 

Troubleshooting

 

E0

 

Ambient temperature sensor  
(White 2 pin connector)

 

Use  a flathead screw  driver to  pry  open  the  display panel. 
Ensure the white 2pin connector is seated properly. Replace 
the sensor or the display panel if needed

 

E1

 

Evaporator temperature sensor 
(Red 2 pin connector)

 

E1: Use a flathead screw driver to pry open the display panel. 
Ensure  the  red  2pin  connector  is seated  properly.  Replace 
the sensor or the display panel if needed.

 

E2

 

Over-current 

 

Verify there is no short in the wiring harness. Make sure the 
outside  fan  and  the  side/bottom  air inlet  are not  blocked. 
Rinse the condenser with water to clean off elements.

 

E3

 

Blocked rotor 

 

Contact customer service

 

E4/EL

 

Low-voltage

 

Check the system and battery voltage. By default, this error 
code triggers when  voltage drops below 10.5V/21.5V  Make 
sure the wiring is connected  properly and there is no  loose 
nuts or crimps

 

E5

 

Short protection/faulty controller

 

Contact customer service

 

E6/EH

 

Over-voltage

 

Check the system voltage. It should be less than 15V/30V

 

E7

 

Compressor startup failure

 

Contact customer service

 

E8

 

Condenser fan

 

Make sure condenser fan connector is seated properly. 

 

EF

 

Evaporator blower fan

 

Make sure the blower fan connector  is seated properly. Pry 
open the display panel and make sure the fuse is intact. 

 

Eb

 

Controller lack-phase

 

Contact customer service

 

EU

 

Controller overheated

 

Let the unit sit for ten minutes and restart the unit

 

 
 
 
 
 
 
 
 
 

Summary of Contents for 2000U

Page 1: ...1 Page DC Under bench Air Conditioner Instruction Manual...

Page 2: ...chat box at velitcamping com Table of Contents 1 IMPORTANT SAFETY INFORMATION 3 1 1 Understand Signal Words 3 1 2 General Safety Message 3 2 SPECIFICATIONS 4 3 ACCESSORIES 5 4 INSTALLATION 6 4 1 Exha...

Page 3: ...tices NOT related to physical injury 1 2 General Safety Message This unit MUST be installed and repaired by qualified personnel who are familiar with the risks involved Do NOTmodify this product in an...

Page 4: ...Voltage 12V 24V 48V Operating Current 20 60A 10 33A 5 15A Cooling Capacity 8000BTU 2200W Air Flow Rate 400mc h Rated Power 700W Refrigerant R134a 400g Noise Level Eco mode 50dB Boost mode 60dB Dimensi...

Page 5: ...plate 2 64mm Air Duct 6ft 2 Air Vent 2 Air Duct Clamp 2 External ControlPanel with 6ft wiring 1 Drain Hose 1 5ft 1 L Drain Hose Adaptor 2 Remote 1 Wiring Harness 6ft 1 Cutting template set 1 1 Air Ve...

Page 6: ...e ENTIRE installation section before starting to ensure the smoothest installation process The general process should follow the order below Failure to do so can result time consuming re work 1 Identi...

Page 7: ...angular hole needs to be cut This approach is easier and faster for installation Two square holes The intake and exhaust vents are mounted separately Two square holes need to be cut This configuration...

Page 8: ...the vent and the unit Make sure the vent location has free airflow and is free of direct obstruction within 8 inches Make sure the fins on the vents do not point at each other Cut the hole using the...

Page 9: ...Place the vent over the opening Secure the vent to the floor with four self tapping screws Apply sealant to the edge of the vent if needed Vent through the wall Leave enough room for the vent and the...

Page 10: ...e sure the vent location has free airflow and is free of direct obstruction within 8 inches Cut the opening using the template Apply sealant paint to any bare metal edges Connect one end of the duct t...

Page 11: ...place the trim over the opening Use self tapping screws to secure the inside vent piece to the outside vent piece Connect the ducts to the unit Use hose clamp to secure the duct Use the foam block to...

Page 12: ...ain line to the outlet before securing the unit to the floor because the outlet will not be accessible once the unit is secured in place Drill a inch 12mm hole on the floor within 1 5ftof the drain ou...

Page 13: ...unit with corner brackets two on each side and one in the frontand back If one side is against the wall no brackets are needed for that side Refer to the drain hose section install the L drain hose ad...

Page 14: ...ired location 4 5 External Control Panel Optional The external control panel can be connected for easier access and better remote reception Pull out the extension connector out from the bottom of the...

Page 15: ...x Listen to the sound pitch of the blower fan and feel the air volume Close the access panel cabinet door Make sure there is no obvious changein blower fan sound pitch and air volume If there is a not...

Page 16: ...or two seconds to turn off the unit Long press ten seconds to reset to factory default setting 2 Mode Switch short press to switch between operating modes Output from low to high output Sleep Eco Cool...

Page 17: ...When unit is on short press to cycle through modes Long press two seconds to turn off the unit Long press ten seconds to reset to factory default setting 2 Temperature Increase setting temperature 3...

Page 18: ...s is a general purpose remote Some buttons do not apply to this model Turn ON OFF Switch between modes Change fan speed Increase temp Decrease temp Sleep mode ECO mode Cooling mode Turbo mode View vol...

Page 19: ...e is lower than the cut off voltage default 10 5 21 5V and thelow voltagered light will light up The unit will turn on automatically once the supplied voltage is higher than the recover voltage defaul...

Page 20: ...here is no short in the wiring harness Make sure the outside fan and the side bottom air inlet are not blocked Rinse the condenser with water to clean off elements E3 Blocked rotor Contact customer se...

Page 21: ...e nominal value use a R134a rechargekit can be purchased fromAuto part stores and Home Depot to charge the unit to the desired pressure If there is oil or other signs of a refrigerantleakage reach out...

Page 22: ...22 Page...

Reviews: