14
Recommended sequence of operations
Operation instructions
cgm.
3
ENA type
IG-235-EN version 02
Fig. 2.14:
Earthing operation from open position
in
cgm.
3-p
2.4.5
Selection of recommended fuses
The fuses recommended for use in the fuse protection
functional unit are defined according to tests carried out by
the manufacturers. The following table shows the
recommended fuse ratings according to the U
r
/P
transf.
ratio:
Remarks:
►
General operating conditions: Without overload,
and temperature < 40 °C.
►
The values marked with an
(
*
)
correspond to SSK-
type fuses.
►
Maximum permitted power loss for a fuse: < 75 W.
►
Recommended fuses: SIBA 20/36 kV, type HH,
medium type striker, for functional units up to 36 kV
and SIBA HHD TB 36 kV, medium type striker, for
functional units up to 36 kV (conforming to
IEC 60282-1).
►
For other brands of fuses and for protection with
overload, consult
Ormazabal
.
►
Temperature-rise testing of the fuse switch
assembly, according to IEC 62271-105.
Transfer current according to IEC 62271-105:
The transfer current has been tested according to the
following parameters:
U
r
[kV]
Transformer rated power [kVA]
Rated fuse current (A) IEC 60282-1
Line
switch-
gear
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
2000
25
36
6,3
10
16
16
16
20
20
31.5
31.5
40
40
50
63
80*
30
36
6,3
6,3
10
16
16
16
20
20
31.5
31.5
40
40
63
63
U
r
Fuse
[kV]
U
r
switchgear
[kV]
I
r
Fuse
[A]
I
transfer
[A]
36
36
SSK type
80
820