Aqua-Hot Hydronic Heating System Shop Manual 09/04
®
SECTION 7: TROUBLESHOOTING
Section 7.6,
continued
Section 7.6,
continued
If the
Fuel Nozzle
is functioning properly:
Continue troubleshooting.
Q3 : Is the Diesel-Burner’s
Motor
operating at
the proper RPM speed?
I.
In order to determine if the
Motor
is operat-
ing properly, reference Section 8.3 and
perform the Motor’s “RPM Test.”
A:
If the
Motor
is not operating at the proper
RPM:
The
Motor
must be replaced;
reference Section 8.3 for replace-
ment instructions.
If the
Motor
is operating at the proper
RPM:
Continue troubleshooting.
Q4 : Is the Diesel-Burner’s
Combustion Air
Intake
adjusted properly?
A:
See the “NOTE” below.
NOTE (7.6-D):
In order to determine if the
Diesel-Burner’s
Combustion Air
Intake
is adjusted
properly, a CO Gas-Analyzer will be required;
reference “Illustration 7.6-3.” Also, reference
Section 11 for the Bacharach Fyrite CO Analyzer’s
part number information, if necessary.
I.
When using the Bacharach Fyrite CO
Analyzer, turn the
“Diesel”
switch
ON
and
allow the
Diesel-Burner
to ignite and operate
for approximately 2 minutes. Then
perform the following procedures:
1. Place the small end of the CO
Analyzer’s suction hose into
the Aqua-Hot’s
Exhaust Pipe
.
2. Place the round plunger
connection of the suction hose
on the CO Analyzer’s
“Plunger.” Press down on the
suction hose with the palm of
your hand until the CO
Analyzer’s “Plunger” is fully
compressed. This will allow a
sample of the Aqua-Hot’s
exhaust to enter the CO
Analyzer; reference
“Illustration 7.6-3.”
2
2
2
2
2
2
2
CO -
2
+ CO2
Combustion Air Intake
Adjustment
13
12
11
10
9
8
7
20
24 26
22
28
10
12
14
DC Voltage Level
V-
Vol %
CO2
CO
2 -
Value Chart
Percentage
CO
2
Gas
Analyzer
#3 - Plunger
#4 - Rubber Ball
Illustration 7.6-3
Page 32