4 Mounting
4.1 Mounting instructions
VEGATOR 131 is designed for carrier rail mounting (top hat rail
35 x 7.5 according to DIN EN 50022/60715). Due to its protection
rating of IP 20, the instrument is suitable for mounting in switching
cabinets. It can be mounted horizontally and vertically.
Note:
When several instruments are mounted together without space in
between, the ambient temperature at the installation location of the
instrument must not exceed 60 °C. Around the ventilation slots there
must be a distance of at least 2 cm to the next component.
The VEGATOR 131 in Ex version is an associated, intrinsically safe
instrument and must not be installed in hazardous areas. Safe opera
-
tion is only ensured if the operating instructions and EU Type Approval
Certificate are observed. VEGATOR 131 must not be opened. A
certification for Ex Zone 2 is also available as an option.
The instrument is suitable for standard ambient conditions acc. to
DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1.
Make sure that the degree of contamination specified in chapter
"
Technical data
" meets the existing ambient conditions.