Vega VEGATOR 122 Operating Instructions Manual Download Page 1

Operating Instructions

Double channel controller for level 

detection for 8/16 mA sensors

VEGATOR 122

Document ID: 46108

Summary of Contents for VEGATOR 122

Page 1: ...Operating Instructions Double channel controller for level detection for 8 16 mA sensors VEGATOR 122 Document ID 46108...

Page 2: ...structions 9 5 Connecting to power supply 10 5 1 Preparing the connection 10 5 2 Connection procedure 11 5 3 Wiring plan 12 6 Setup 13 6 1 Adjustment system 13 6 2 Adjustment elements 13 6 3 Function...

Page 3: ...210714 10 4 Trademark 27 Supplementary documentation Information Supplementary documents appropriate to the ordered version come with the delivery You can find them listed in chapter Product descrip...

Page 4: ...tering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successful work Note This symbol ind...

Page 5: ...a state of the art instrument complying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi b...

Page 6: ...n Canada shall comply with the relevant requirements of the Canadian Electrical Code 2 6 Safety instructions for Ex areas For applications in explosion proof areas Ex only devices with cor responding...

Page 7: ...can find all via your smartphone Scan the QR code on the type label of the device or Enter serial number manually in the VEGA Tools app available free of charge in the respective stores 3 2 Principle...

Page 8: ...ling companies Transport must be carried out in due consideration of the notes on the transport packaging Nonobservance of these instructions can cause damage to the device The delivery must be checke...

Page 9: ...und the ventilation slots there must be a distance of at least 2 cm to the next component VEGATOR 122 in Ex version is a corresponding intrinsically safe in strument and must not be installed in hazar...

Page 10: ...of EN 61326 for industrial areas shielded cable should be used Make sure that the cable used has the required temperature resist ance and fire safety for max occurring ambient temperature Connect the...

Page 11: ...d as follows 1 Mount the instrument as described in the previous chapter 2 Connect sensor cable 1 to terminal 1 2 and where applicable connect the shielding 3 Connect sensor cable 2 to terminal 4 5 an...

Page 12: ...1 8 16 mA max level with two point control 2 Sensor circuit channel 2 8 16 mA min level with two point control 3 Relay output channel 1 4 Relay output channel 2 5 Voltage supply Information The conne...

Page 13: ...ignal lamps LEDs 4 Hinged front cover 6 2 Adjustment elements Control lamps LED in the front plate indicate operation switching status and fault signal Green Operating control lamp Mains voltage on in...

Page 14: ...delay 6 seconds 7 Two point control On Off 8 Mode min max adjustment channel 2 The requested operating mode is set with the min max switch min detection i e dry run protection or max detection i e ov...

Page 15: ...control two point control allows the switch on and switch off points to be set at different locations hyster esis Through the installation or the distance of the two sensors the hysteresis can be def...

Page 16: ...to WHG 6 3 Function table Point level The following table provides an overview of the switching conditions depending on the set mode and the level Note The switching conditions in the tables are only...

Page 17: ...onditions depending on the set mode and the level Note The switching conditions in the tables are only valid if the mode switch on the sensor is set to Max Sensor Controller Level Sensor cur rent LED...

Page 18: ...evel Sensor cur rent LED yellow output LED red fault Relay approx 8 mA approx 8 mA OFF approx 8 mA approx 16 mA OFF approx 16 mA approx 16 mA ON approx 8 mA approx 16 mA ON approx 8 mA approx 8 mA OFF...

Page 19: ...many cases the causes can be determined this way and faults can be easily rectified Depending on the reason for the fault and the measures taken the steps described in chapter Setup must be carried o...

Page 20: ...or or sensor cable Reconnect the sensor cable to the controller disconnect the sensor and replace it with a 1 k resistor If the fault signal does not disappear then the sensor cable is broken replace...

Page 21: ...ut one form per instrument Clean the instrument and pack it damage proof Attach the completed form and if need be also a safety data sheet outside on the packaging Ask the agency serving you to get th...

Page 22: ...te of chapters Mounting and Connecting to voltage sup ply and carry out the listed steps in reverse order 8 2 Disposal The device is made of recyclable materials For this reason it should be disposed...

Page 23: ...und on our homepage 9 3 SIL conformity optional Instruments with SIL option fulfill the requirements of functional safety according to IEC 61508 You can find further information in the sup plied Safet...

Page 24: ...re cross section 0 25 mm AWG 23 2 5 mm AWG 12 Voltage supply Operating voltage Nominal voltage AC 24 230 V 15 10 50 60 Hz Nominal voltage DC 24 65 V 15 10 Max power consumption 3 W 8 VA Sensor input Q...

Page 25: ...conditions Vibrations oscillations Class 4M4 acc to IEC 60721 3 4 1 g 4 200 Hz Impacts mechanical shock Class 6M4 acc to IEC 60721 3 6 10 g 11 ms 30 g 6 ms 50 g 2 3 ms Electrical protective measures...

Page 26: ...ed approval documents of these instruments have to be carefully noted They are part of the delivery or can be downloaded by entering the serial number of your instrument into the search field under ww...

Page 27: ...www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de produc...

Page 28: ...4 E Ex version 9 F Fault Fault signal 19 Fault rectification 19 G Grounding 10 H Hysteresis 15 L LEDs 13 M Mode 14 O Overflow protection 14 P Potential equalisation 10 Protection rating 9 Q QR code 7...

Page 29: ...29 Notes VEGATOR 122 46108 EN 210714...

Page 30: ...30 Notes VEGATOR 122 46108 EN 210714...

Page 31: ...31 Notes VEGATOR 122 46108 EN 210714...

Page 32: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...