86
10 Supplement
VEGAPULS 69 • Modbus and Levelmaster protocol
47252-EN-210205
Set Receive to Transmit Delay
Parameter
Length
Code/Data
Request:
Set Receive to Transmit
Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Set Receive to Transmit
Delay
6 characters ASCII
UuuROK
Report Number of Floats
Parameter
Length
Code/Data
Request:
Set Receive to Transmit
Delay
4 characters ASCII
UuuF
Response:
Set Receive to Transmit
Delay
5 characters ASCII
UuuFn
n = number of measurement values
(0, 1 or 2)
Report Receive to Transmit Delay
Parameter
Length
Code/Data
Request:
Report Receive to Transmit
Delay
4 characters ASCII
UuuR
Response:
Report Receive to Transmit
Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to
250), default = 127 ms
Error codes
Error Code
Name
EE-Error
Error While Storing Data in EEPROM
FR-Error
Erorr in Frame (too short, too long, wrong data)
LV-Error
Value out of limits