6 Set up the sensor with the display and adjustment module
VEGAPULS 69 • Modbus and Levelmaster protocol
47252-EN-210205
4. Enter the corresponding distance value in meters for the full ves-
sel.
5. Save settings with
[OK]
and move with
[ESC]
and
[->]
to Min.
adjustment.
Proceed as follows:
1. Select with
[->]
the menu item "
Min. adjustment
" and confirm with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
4. Enter the suitable distance value in m for empty vessel (e.g. dis-
tance from the sensor to the vessel bottom) corresponding to the
percentage value.
To damp process-dependent measured value fluctuations, set an
integration time of 0 … 999 s in this menu item.
The default setting is a damping of 0 s.
In the menu item "
Current output mode
" you determine the output
characteristics and reaction of the current output in case of fault.
The default setting is output characteristics 4 … 20 mA, fault mode
< 3.6 mA.
Setup - Min. adjustment
Setup - Damping
Setup - Current output,
mode