44
6 Set up the sensor with the display and adjustment module
VEGAPULS 69 • Modbus and Levelmaster protocol
47252-EN-210205
2
1
3
100%
0%
1
m
(39.37
")
35
m
(1378
")
Fig. 37: Parameterisation example, Min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
3 Reference plane
If these values are not known, an adjustment with the distances of e.g.
10 % and 90 % is possible. Starting point for these distance specifica
-
tions is always the sealing surface of the thread or flange. You can find
specifications on the reference plane in chapter "
Technical data
". The
actual level is calculated on the basis of these settings.
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Proceed as follows:
1. Select with
[->]
the menu item Max. adjustment and confirm with
[OK]
.
2. Prepare the percentage value for editing with
[OK]
and set the
cursor to the requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
Setup - Max. adjustment