5 Set up with the display and adjustment module PLICSCOM
VEGAPULS 65 • 4 … 20 mA/HART - four-wire
51885-EN-160621
5.2 Setup steps
1. Go to the menu "
Basic adjustment
" via the display and adjust-
ment module.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Carry out the adjustment in the menu items "
Min. adjustment
" and
"
Max. adjustment
".
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3. Select in the menu item "
Medium
" the medium of your applica-
tion, for example "
Aqueous solution
".
Medium
Liquid
4. Select in the menu item "
Application
" the vessel, the application
and the vessel form, for example, "
Storage tank
".
Vessel form
Storage tank
The radar sensor measures the distance from the sensor to the
product surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
Set parameters
Parameterization example