41911-EN-200522
y
x
Fig. 15: Mounting adapter "High temperature with extension" -40 … +450 °C
(-40 … +842 °F) for front-flush mounting
x Length: Mounting adapter "High temperature"
y Extension length 40, 60, 80, 100 or 150 mm (1.57, 2.36, 3.15, 3.94, 5.91 in)
In case of strong vessel vibrations, the VEGAMIP 62 should be
mounted with anti vibration blocks or rubber buffers.
1
2
Fig. 16: Installation with vessel vibrations
1 Anti vibration blocks or rubber buffers
2 Window of non-conductive material, for example, glass, plastic, etc.
Angle
To get an optimal switching signal, the two sensors must be aligned to
each other. The accuracy must be in a range of ±5°.
Axis offset
The axes of the two sensors can be offset up to < 5% of the sensor
distance (d) from each other. Example: with a distance of 1000 mm
Vibrations
Orientation of the sensor