30
7 Set up with the integrated display and adjustment unit
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
the number of switch-on events can also be displayed. The counters
can also be reset.
The simulation of a measured value is used to check the outputs and
connected components. It can be applied to the sensor value, the per-
centage value, the lin. percentage value as well as the scaled value.
Note:
Please note that downstream plant components (valves, pumps,
motors, controls) are influenced by the simulation, which can lead
to unintentional plant operating states. The simulated value is output
until you deactivate the simulation mode again. The simulation is
automatically terminated after approx. 60 minutes.
You can assign an unambiguous name to VEGAMET 861 to the
Device-TAG via DTM/VEGA Tools app. This function is recommended
when several instruments are implemented and a good documenta-
tion of larger systems is required.
The menu item "
Device information
" provides the device name and
serial number as well as the hardware and software version.
The measured values saved on the internal device memory can also
be copied to an SD card inserted in the device. To do this, use the
menu item "
Copy to SD card
".
Before removing an inserted SD card, use the "
Remove SD card
safely
" function to remove the card safely and without data loss from
the device.
Further information on saving measured values can be found in chap-
ter "
Measured value memory/data logger
".
Simulation
Device-TAG
Device information
Device memory