11 Diagnostics and servicing
VEGAMET 342 • 4 … 20 mA
63731-EN-221107
occur or in case of incorrect parameter adjustment, a fault signal is
triggered. In case of an instrument defect or line break/shortcircuit, a
fault signal is also triggered.
The fault indication lights up in case of failure and the current output
as well as the relays react according to the configured fault mode. If
the fail safe relay was configured, it will deenergize. In addition, one
of the following error messages is outputted on the display and the
background lighting changes to colour acc. to NAMUR NE 107 (e.g.
red in case of a fault, orange in case of a function check).
Error code
Cause
Rectification
F002
no measuring
point configured
Measuring point
was not yet con-
figured
No sensor assigned.
For measuring point 3: No application
with 3 measuring points was selected.
F003
Hardware: CRC
error
CRC error (error
with self-check)
Switch the instrument off/on
Carry out a reset
Send instrument for repair
F012
Sensor input:
Hardware error
Hardware error,
sensor input
Switch the instrument off and on
Send instrument for repair
F013
Sensor input:
Sensor error
The input of the
measuring point
returns an error
The connected
sensor returns
an error
Switch device/sensor off an on
Send device/sensor for repair
F014
Sensor input:
Short-circuit
Sensor cur-
rent > 21 mA or
short-circuit
Check sensor, e.g. on fault signal
Remove short-circuit
F015
Sensor input:
Line break
Sensor in boot
phase
Sensor current
< 3.6 mA or line
break
Check sensor, e.g. on fault signal
Remove line break
Check connection of the sensor
F034
EEPROM: CRC
error
EEPROM: CRC
error
Switch the instrument off and on
Carry out a reset
Send instrument for repair
F035
ROM: CRC error
ROM: CRC error Switch the instrument off and on
Carry out a reset
Send instrument for repair
F036
No operable
software
No executable
program
Software update
failed
Carry out another software update
Send instrument for repair
F037
RAM
RAM defective
Switch the instrument off and on
Carry out a reset
Send instrument for repair
Failure