4 Mounting
VEGAMET 342 • 4 … 20 mA
63731-EN-221107
4 Mounting
4.1 General instructions
The device is designed for recessed installation in a switching cabi-
net, housing front panel or switch cabinet door. The required cut-out is
92 x 92 mm (3.63 x 3.63 in) according to IEC 61554.
A VEGAMET 342 in Ex version is an auxiliary, intrinsically safe instru-
ment and may not be installed in explosion-endangered areas.
The instrument is suitable for standard and extended ambient condi-
tions acc. to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1.
Make sure that the environmental and ambient conditions specified in
chapter "
Technical data
" are maintained.
4.2 Mounting instructions
1. Make sure that the cut-out required for mounting has a size of
92 x 92 mm (3.63 x 3.63 in).
2. Slide the device into the panel cut-out from the front.
3. Press the two tensioning elements into the provided gaps.
4. Screw in the two screws of the tensioning elements evenly with a
screwdriver.
3
2
1
Fig. 3: Front panel mounting
1 Front panel, front plate or switching cabinet door
2 Clamping elements
3 Slotted screw
Mounting options
Ambient conditions
Front panel mounting