5 Set up the sensor with the display and adjustment module
VEGABAR 83 • Modbus and Levelmaster protocol
46318-EN-220624
The main menu is divided into five sections with the following func
-
tions:
Setup:
Settings e. g. for measurement loop name, application, units,
position correction, adjustment, signal output, disable/enable opera
-
tion
Display:
Settings, e.g., for language, measured value display, lighting
Diagnosis:
Information, for example, of device status, peak value,
simulation
Additional adjustments:
date/time, reset, copy function
Info:
Instrument name, hardware and software version, calibration
date, sensor features
Note:
For optimum setting of the measuring point, the individual submenu
items in the main menu item "
Setup
" should be selected one after
the other and provided with the correct parameters. If possible, go
through the items in the given sequence.
The submenu points are described below.
5.4 Menu overview
The following tables show the adjustment menu of the instrument.
Depending on the instrument version or application, all menu items
may not be available or some may be differently assigned.
Setup
Menu item
Parameter
Default value
Measurement loop name
Sensor
Application
Application
Level
Secondary sensor for electronic differen
-
tial pressure
Deactivated
Units
Unit of measurement
mbar (with nominal measuring range
≤ 400 mbar)
bar (with nominal measuring ranges
≥ 1 bar)
Temperature unit
°C
Position correction
0.00 bar
Adjustment
Zero/Min. adjustment
0.00 bar
0.00 %
Span/Max. adjustment
Nominal measuring range in bar
100.00 %
Damping
Integration time
1 s
Main menu