6.3.3 Diagnostics
In this menu item, you can enquire the status of your sensor. In normal
operation, the sensor displays the message "
OK
". In case of fault,
you will find the corresponding fault code here.
The peak value function holds the max. and min. values during opera-
tion.
•
Pulse rates - min./max.
•
Temperature - min./max./actually
Here you can retrieve the adjustment value of the sensor. This is the
percentage value of the difference of the min. and max. adjustment
points (Delta I). The value is an indication for the reliability and non-
repeadability of the measurement.
The higher the difference between the two adjustment points,
the higher the differential value (Delta I) and the more reliable the
measurement. A Delta I value below 10 % is an indication for a critical
measurement.
To increase the Delta I value, you have to increase the distance of the
min. and max. adjustment points in the linearization.
In this menu item you can simulate measured values via the signal
output. This allows the signal path to be tested, e.g. through down-
stream indicating instruments or the input card of the control system.
Note:
To carry out a simulation with the display and adjustment module,
you have to switch on the simulation switch on the electronics module
(switch position 1).
You can find the rotary switch on the electronics module in the elec-
tronics and connection department (large cover).
You can simulate different values:
Device status
Peak value indicator
Adjustment data
Simulation