background image

 

Vega SI-11 / User Manual 
  

 

15

 

Revision 26 of 25 August 2021  

 

"Values of basic settings" bit field decoding  

Bit 

Meaning 

0 bit 

Activation type: 0 - OTAA, 1 – ABP 

1, 2,3 bits 

Communication period: 
|1 == 0|2==0|3==0| - 5 minutes 
|1 == 1|2==0|3==0| - 15 minutes 
|1 == 0|2==1|3==0|- 30 minutes 
|1 == 1|2==1 |3==0|- 1 hour 
|1 == 0|2==0|3==1|- 6 hours 
|1 == 1|2==0|3==1|- 12 hours 
|1 == 0|2==1|3==1|- 24 hours 
 

4 bits 

First input type: 0 – pulse, 1 - security 

5 bits 

Second input type: 0 – pulse, 1 - security 

6 bits 

Third input type: 0 – pulse, 1 - security 

7 bits 

Fourth input type: 0 – pulse, 1 - security 

Time zone considered during collection data from an external meter. 

2.

 

«Alarm» packet  

Sent in case of security input closure on LoRaWAN port 2. 

Size in bytes 

Field description 

Data type 

1 byte 

Packet type, this packet == 2 

uint8 

1 byte  

Battery charge, % 

uint8 

1 byte 

Values of basic settings (bit field) 

uint8 

1 byte 

Input No, where the alarm is detected  

uint8 

4 bytes 

Packet time (unixtime UTC) 

uint32 

4 bytes 

 

Input 1 reading (depending on the type – number of pulses or 
status: 0 – open, 1 - closed) 

uint32 

4 bytes 

Input 2 reading (depending on the type – number of pulses 
or status: 0 – open, 1 - closed) 

uint32 

4 bytes 

Input 3 reading (depending on the type – number of pulses 
or status: 0 – open, 1 - closed) 

uint32 

4 bytes 

Input 4 reading (depending on the type – number of pulses 
or status: 0 – open, 1 - closed) 

uint32 

When sending alarm packet, the device uses the data taken at moment of alarm triggers. 

3.

 

Packet with time correction request 

Sent every seven days on LoRaWAN port 4. 

Size in bytes 

Field description 

Data type  

1 byte 

Packet type, this packet == 255 

uint8 

4 bytes 

Time of the modem at a moment of the packet transmission 
(unixtime UTC) 

uint32 

Summary of Contents for SI-11

Page 1: ...www vega absolute ru PULSE COUNTER VEGA SI 11 USER MANUAL DOCUMENT REVISION FIRMWARE VERSION 26 2 4...

Page 2: ...LED Indications 11 Mounting Recomendations 12 4 COMMUNICATION PROTOCOL 14 Vega SI 11 pulse counter transmits the following types of packets 14 1 Packet with current readings 14 2 Alarm packet 15 3 Pa...

Page 3: ...ation on powering and activation procedure control commands and functions of the counter This manual is targeted at specialists familiar with installation work fundamentals of electronic and electrica...

Page 4: ...t in fire OPERATION ALGORITHM Vega SI 11 operates in modes listed below Storage is a mode for storing and transporting In this mode the device does not communicate regularly with the network Active is...

Page 5: ...m 5 minutes to 24 hours When beginning of communication session the device starts sending packets with readings from the earliest packet The time of data transmitting cannot be specified it s defined...

Page 6: ...easuring of the built in battery MARKING Device marked with sticker that contain the next information Device name DevEUI Release Date Sticker located in three places on device case in factory certific...

Page 7: ...mmunication period 5 15 30 minutes 1 6 12 or 24 hours Data collection period 5 15 30 minutes 1 6 12 or 24 hours Memory amount for storing packets 200 packets Type of the LoRaWAN antenna internal Sensi...

Page 8: ...t Delay 5 seconds Uplink number of transmissions 1 Data rate DR0 Power 14 dBm Communication period 24 hours Data collection period 24 hours Time zone UTC 00 00 Inputs operate in mode pulse For changin...

Page 9: ...mounting for DIN rail 1 screw 2 mm 8 mm cross 2 DIN rail with mounting holes 3 mm 3 silicone gasket without through holes ensuring the protection rating of the device case IP65 All of elements for ma...

Page 10: ...t is not supported Polarity effects only open collector circuits To reset all readings from the pulse inputs accumulated in the device memory you need to switch the device to the Storage mode by holdi...

Page 11: ...ANING Short flashings Linking to the network in progress One long flashing during 5 sec The device has been successfully connected to the network and is in active mode Three flashings each by 1 sec Li...

Page 12: ...ed screwdriver awl wire stripper laptop Step by step mounting be like 1 Setting the devices and connecting them to the network are usually carried out in the office see Network Deployment Manual 2 Det...

Page 13: ...device it is necessary to reset the pulses accumulated during testing and connection by switching the device to the Storage mode by pressing the button for 5 seconds 9 Start the device by pressing lau...

Page 14: ...ing on the type number of pulses or status 0 open 1 closed uint32 4 bytes Input 2 reading depending on the type number of pulses or status 0 open 1 closed uint32 4 bytes Input 3 reading depending on t...

Page 15: ...this packet 2 uint8 1 byte Battery charge uint8 1 byte Values of basic settings bit field uint8 1 byte Input No where the alarm is detected uint8 4 bytes Packet time unixtime UTC uint32 4 bytes Input...

Page 16: ...en settings request command received or device connected to the network Size in bytes Field description Data type 1 byte Packet type this packet 0 uint8 2 bytes ID of parameter uint16 1 byte Data leng...

Page 17: ...device sends the packet with settings 3 Packet with settings Is identical to such packet from device Size in bytes Field description Data type 1 byte Packet type this packet 0 uint8 2 bytes ID of para...

Page 18: ...yte 1 pulse 2 guard 14 Input 3 mode 1 byte 1 pulse 2 guard 15 Input 4 mode 1 byte 1 pulse 2 guard 16 Communication period 1 byte 1 1 hour 2 6 hours 3 12 hours 4 24 hours 5 5 minutes 6 15 minutes 7 30...

Page 19: ...ION REQUIREMENTS Vega SI 11 pulse counter shall be stored in the original packaging in heated room at temperatures 5 to 40 and relative humidity less than 85 The counter shall be transported in covere...

Page 20: ...Vega SI 11 User Manual 20 Revision 26 of 25 August 2021 6 CONTENT OF THE PACKAGE The pulse counter is delivered complete with Vega SI 11 pulse counter 1 pc Screw 4 pcs Factory certificate 1 pc...

Page 21: ...ory certificate the factory certificate does not have an TCD stamp and or there is no sticker with information about the device the serial number DevEUI EMEI printed on the product differs from the se...

Page 22: ...17 PKP Fixed error in protocol description 13 16 08 2017 PKP Adding s in alarm command description 14 08 09 2017 KEV Part Vega LoRaWAN Configurator was added 15 11 10 2017 KEV Warranty was changed min...

Page 23: ...ixed inaccuracy about data type in Temperature field minor changes 24 09 06 2020 KEV The battery information is changed in the specification 25 24 06 2021 KEV Scheduled revision of documentation New w...

Page 24: ...Vega SI 11 User Manual 24 Revision 26 of 25 August 2021 vega absolute ru User Manual Vega Absolute OOO 2017 2021...

Reviews: