6 Set up with the display and adjustment module
MINITRAC 31 • Foundation Fieldbus
41782-EN-211203
Menu
Menu item
Default value
Setup
Measurement loop name
Sensor
Isotope
Cs-137
Application
Limit level
Adjustment mode
Single point adjustment
Adjustment - uncovered
90000 ct/s
Adjustment - covered
9000 ct/s
only with two-point adjustment
Delta I
90 %
Background radiation
0 ct/s
Temperature unit
° C
Adjustment mode
1-point
Adjustment uncovered
900000 ct/s
Delta I
90 %
Mode - Relay
Overfill protection
Lock adjustment
Released
Display
Language
Selected language
Displayed value
Pulse rate
Display unit
ct/s
With this function
•
Load parameter adjustment data from the sensor into the display
and adjustment module
•
Write parameter adjustment data from the display and adjustment
module into the sensor
The copied data are permanently saved in an EEPROM memory in
the display and adjustment module and remain there even in case of
a power failure. From there, they can be written into one or more sen-
sors or kept as backup for a possible sensor exchange.
Note:
Before the data are copied into the sensor, a check is carried out to
determine if the data fit the sensor. If the data do not fit, a fault signal
is triggered. When data are being written into the sensor, the display
shows which instrument type the data originate from and which TAG
number this sensor had.
6.5.5 Info
In this menu you will find the following menu items:
•
Instrument name - shows instrument name and serial number
Copy instrument settings
Info