Introduction
Alarm Message Quick Reference Index
4
Alarm Message Quick Reference Index
Table 1:
Alarm Message Table
Alarm
Type
Cause
Action
Annual Test Fail
Tank
In-tank annual leak test failed
Rerun in-tank leak test. If second test fails,
call for service.
Autodial Fail
Comm
System failed to connect to a remote
receiver after programmed number of
tries.
Check remote receiver.
Delivery Needed
Tank
Product level dropped below preset
limit.
Call for delivery.
Gross Test Fail
Tank
In-tank leak test failed.
Rerun in-tank leak test. If second test fails,
call for service.
High Water
Tank
Water detected in tank exceeds preset
limit.
Remove water from the tank.
Invalid Fuel Height
Tank
Fuel level dropped to a point below
the minimum detectable level or only
one float is present.
Call for delivery.
Low Product
Tank
Tank level dropped below preset limit.
Call for delivery.
Low Temperature
Tank
Probe temperature dropped below -
4°F (-20°C). For Low Temperature
probes, below -40°F (-40°C).
Probe returns to normal operation after
probe temperature rises above 0°F
(-17.7°C). For Low Temperature probes,
above -36°F (-38°C)
Max Product
Tank
Product level rose above preset limit.
Stop delivery.
Overfill
Tank
Potential overflow of tank may occur.
Stop delivery. Check for spillage.
Periodic Test Fail
Tank
In-tank leak test failed.
Rerun in-tank leak test. If second test fails,
call for service.
Probe Out
Tank
Hardware failure - probe or intercon-
necting wiring to console.
Call for service.