System Setup Screens
[259-262] EuroProtocol and Stick Offset Setup Screen
44
[259-262] EuroProtocol and Stick Offset Setup Screen
Legend for numbered boxes
01-01-2000
12:00 AM
ALL FUNCTIONS NORMAL
1
2
3
4
[259]
[260]
[261]
[262]
SYSTEM SETUP EURO PROTOCOL & STICK OFFSET
This screen contains international format options and leak test
format setup.
1
H-Protocol Format [259] - Touch the Down Arrow button
to the right of the window and select: Height (default) or
Volume for H-Protocol.
2
Euro Protocol Prefix [260] - Touch the Down Arrow button
to the right of the window and select: S (default) or ‘d’.
3
Stick Height Offset [261] - Touch the Down Arrow button
to the right of the window and select: Enabled or
Disabled (default).
4
Leak Test Format [262] - The leak test report format can
be set to Enhanced to comply with the California Code of
Regulations. The enhanced report will have height, water,
temperature, percent volume, rate and threshold values in
addition to the normal report format. Touch the Down
Arrow button to the right of the window and select:
Normal (default) or Enhanced.