6
Console Installation
Selecting a Console Location
Select a mounting location inside the building. The console must be protected from severe vibration, extremes in
temperature and humidity, rain, and other conditions that could harm computerized electronic equipment.
The equipment is designed to operate safely under the following range of conditions:
• Temperature range 0 to 40°C - (storage temperature range of -20 to +70°C)
• A maximum relative humidity of 95% RH (non-condensing) at temperatures up to 40°C.
• Console may be powered by either 120 or 240 Vac. A switchmode power supply automatically detects the
input voltage (no jumpers required).
• Main supply voltage fluctuations not exceeding ±10%
• Pollution Degree Category 2
• Installation Category II.
Important! This console must be installed inside a building. It is not suitable for any external location. If the unit
requires cleaning, do not use any liquids, wipe only with a clean, dry cloth - Console must be turned Off when
cleaning the display.
Ensure that the console is located where neither the console nor its associated cabling will be damaged by doors,
furniture, barrows, etc. Consider the ease of routing wiring, ducting, and probe cables to the console. Check that
the mounting surface material is strong enough to support the console’s weight of about 5 pounds (2.3 kg).
ACCESSING THE CONSOLE’S MOUNTING HOLES
Open the console door by removing the right side (looking at the front) top and bottom #15 Torx screws. Swing
open the door to the left. The display and CPU board assembly are now visible. Gently lifting on the right side of
the CPU board, swing the CPU mounting plate to the left. The power supply board and Intrinsically safe cover are
now visible. The left top and bottom console mounting holes should be visible. Swing the small Intrinsically safe
area cover to the left and you should see the right top and bottom console mounting holes.
WARNING
Explosive vapors or flammable liquids could be present near locations where
fuels are stored or being dispensed. The console is not explosion proof.
An explosion or fire resulting in serious injury or death, property loss and
equipment damage could occur if the console is installed in a volatile,
combustible or explosive atmosphere (Class I, Division 1 or 2).
Do not install this console in a volatile, combustible, or explosive atmosphere.