TLS-450 Setup and Operation Screens Manual
238
Clear Table
You should manually clear the CSLD Rate Table if data, known to be inaccurate, had been stored in the
table and the source of the inaccurate data was subsequently removed (e.g., after making tank plumbing
repairs).
IMPORTANT! DO NOT CLEAR THE CSLD RATE TABLE UNLESS IT IS ABSOLUTELY
NECESSARY. DATA CLEARED FROM THIS TABLE CAN NOT BE RECOVERED!
Touch the Clear Table button to clear the 30 day CSLD rate table. You will be prompted to confirm this
action. The warning "Are you sure you want to clear the CSLD rate table?" is displayed, with OK and
Cancel buttons. If the OK button is selected, the dialog is closed, the CSLD rate table is cleared, and the
report is refreshed to reflect the change. If the Cancel button is selected, the dialog is closed and the
report view is unchanged. If the Clear Table button is selected when the current tank selection is "All
Tanks", the following error message is displayed: "This operation is valid for a single tank only".
Select Range
Touch this button to setup the report's contents:
•
Select Option List
- Select data for report: All Records, Day, Week, Month, Year, Date Range
•
Period Option List
- Select period: Previous, Previous n selections
•
Select Tank(s)
- Select tank(s) to report: "All Tanks" or "Current Tank"
Regulatory Compliance
Note: In-tank leak tests will not be declared a PASS unless the product level in the tank satisfies the
minimum product level defined in our Third Party certification for the leak test being performed. In-tank
leak tests performed with the product level below these minimum levels will be declared Invalid. Because
the minimum product level requirements vary with local, state, and federal regulations, you need to
ensure that the product level complies with the applicable regulations in your location.