TLS-450 Setup and Operation Screens Manual
107
Stop Time
Allowable selections: HH:MM am/pm. Default:12 pm
Line Lockout Schedule - Individual
Individual schedule allows you to enter up to seven separate lockout schedules. You program each
lockout period with an Event Start day and time, and an Event End day and time. For example, lockouts 1
through 5 could be programmed to lock out the line leak test each day from Monday through Friday to
accommodate hours when the station is closed. Lockout 6 could be programmed to lock out the test from
Friday night to Monday morning if the site is closed for the weekend.
If lockout schedules are programmed incorrectly, the line leak tests may not run. Make sure you have
programmed the settings correctly.
Event Start
Allowable selections: Disabled, Monday - Sunday
Default: Disabled
Start Time
If a start date is selected, a start time is selectable.
Allowable selections: HH:MM am/pm
Default:12 pm
Event End
Allowable selections: Disabled, Monday - Sunday
Default: Disabled
End Time
If an end date is selected, an end time is selectable.
Allowable selections: HH:MM am/pm
Default: 12 pm
Repeat the above procedure for additional Individual Lockout Schedule Event Start/End selections
(up to 5).