Site Prep Certification Manual

TLS-450/TLS-450PLUS Consoles

Summary of Contents for TLS-450

Page 1: ...Manual No 577013 934 Revision E Site Prep Certification Manual TLS 450 TLS 450PLUS Consoles...

Page 2: ...ur Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax...

Page 3: ...ng Adapter 7 Vapor Extraction Riser Kit W O Coupling Adapter 8 Riser Cap Kit for Mag Probe Installations 9 Cap and Cord Grip Kit 9 Metal Cap and Ring Kit 9 Mag Probe Installation UST AST Tank Dedicate...

Page 4: ...beneath the metal cap and adapter ring 12 Figure 12 Vapor extractor cabling entry 13 Figure 13 Mag probe vapor extractor riser installation w coupling adapter 15 Figure 14 Mag probe vapor extractor r...

Page 5: ...Descriptive System IECEx Descriptive System UL cUL Control Drawing Document No Document No Document No Associated Apparatus TLS 450 TLS 450PLUS 331940 006 331940 106 331940 008 Intrinsically Safe Appa...

Page 6: ...such as Carol C2534 or Belden 88760 8760 8770 or similar Note Throughout this manual when mentioning any cable or wire being used for probe and sensor to console wiring it will be referring to shielde...

Page 7: ...o the mounting surface using the hole pattern shown in Figure 1 Up to 1 4 diameter screws may be used Mount the console to the mounting surface using the four mounting flanges on the back of the unit...

Page 8: ...35 BOTTOM VIEW tlsng dim eps Mounting flanges w 1 4 x 3 8 slotted hole typ 4 places 3 1 8 1 2 TYP 5 925 0 65 4 5 8 3 1 8 3 1 8 3 1 8 TOP VIEW Conduit entries to Module bay 3 4 1 I P S knockouts typ 4...

Page 9: ...ious injury or death Routing conduit for power wires into the intrinsically safe compartment can result in fire or explosion resulting in serious injury or death OFF L1 N L2 L1 G L2 To 240 Vac breaker...

Page 10: ...ag Probe AST Installation Kit Table 1 Mag Probe AST Installation Kit Part No 312020 984 Quantity Description Part Number 5 feet 3 8 Flexible Conduit 576008 294 1 3 8 Adapter Nut 329972 002 2 3 8 Strai...

Page 11: ...o 846500 001 Quantity Description Part Number 2 Wire Nut 576008 461 1 Cable Tie 576008 482 1 Splice Enclosure 514100 357 1 Splice Kit Instructions Manual 576013 861 1 PG7 1 4 Cord Grip Fitting 576008...

Page 12: ...oupling Adapter Installation Kit Table 3 Vapor Extraction Riser Kit W O Coupling Adapter Part No 846500 002 Quantity Description Part Number 2 Wire Nut 576008 461 1 Cable Tie 576008 482 1 Splice Enclo...

Page 13: ...screws onto the 4 NPT riser Figure 6 The cap comes drilled and tapped with a cord grip Figure 6 Cap And Cord Grip Kit METAL CAP AND RING KIT This riser cap kit contains an adapter ring which screws o...

Page 14: ...rip fitting P N 331028 001 as follows 1 Remove the cap to a non hazardous location 2 Drill and tap the cap for a 1 2 14 NPT cord grip thread Figure 8 Figure 8 Modifying An Existing Metal Riser Cap 1 C...

Page 15: ...he cord grip bushing and nut on the cap leaving a minimal amount of slack between the probe and cap Screw the cap onto the riser by hand until the gasket first contacts the pipe Then lightly tap the c...

Page 16: ...5 45 ft lbs Loosen the cord grip nut and push the cable through the metal cap and cord grip then clamp the cap onto the ring see Figure 11 Figure 11 Installing A Riser Adapter Beneath The Metal Cap An...

Page 17: ...nut and loosely screw the adapter Nut from the AST kit onto the cord grip fitting see Figure 3 on page 6 Push the cable through the metal cap bushing and adapter nut then clamp the cap onto the ring M...

Page 18: ...additional 3 4 turn 9 Test pull the cable to insure that it is free of spring and that the probe is resting on the bottom of the tank Make sure there is some slack in the cable 10 Slip the PG7 cord gr...

Page 19: ...floats spacer rings and cable as per the Mag Probe Assembly Manual 5 Gently slide the float s to the bottom of the probe shaft Important Handle probes carefully Striking or dropping the probe will re...

Page 20: ...on System you now need to consider another form of overfill protection i e TLS console alarm a drop tube with overfill protection valve or some other accepted means Figure 14 Mag Probe Vapor Extractor...

Page 21: ...plicing all sump sensor wires together to run one wire back to console Use single lengths of wire with no splices to ensure optimum signal strength Figure 15 Example Probe Wiring Run In Buried Rigid C...

Page 22: ...g using an abrasive wheel a 1 4 to 3 8 wide by 1 1 4 deep groove adding 1 4 of depth for each additional cable in the pavement surface laying Veeder Root supplied direct burial cable down in the botto...

Page 23: ...ve sys or dispenser 120 240 Vac Output Relay Connections Pump Sense Pump In Pump Return NO C Dispenser Control Connections External Input Connections NO C SWITCH HOOK STP CONTROL w RJ Relay Control Bo...

Page 24: ...DIM L1 N NC NC P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 120 VAC INPUT RATING 120 VAC MAX 0 30 AMP MAX White 934 2 eps Black 115 Vac Line BLK Neutral WHT Barrier P N 7859 769780 008 Pulse Transmitter 120...

Page 25: ...ition Common Pulser 12 PetroVend System 2 PV270 Pump Relay Board LVDIM LOW VOLTAGE DISPENSER INTERFACE MODULE 12 11 10 9 5 6 7 8 1 2 3 4 SOURCE INPUT RATING 30 VDC MAX 0 1 AMP MAX 934 1 eps Micon 200...

Page 26: ...For technical support sales or other assistance please visit www veeder com...