In-Tank Leak Tests
Leak Test Frequency
8-4
Press STEP to continue. The system displays the START TIME message. Follow the procedure under “Leak Test
Start Time” on page 8-7.
WEEKLY TEST
To run the tests weekly,
press CHANGE three times, then press ENTER in response to the ON DATE message:
The system displays the message:
Press STEP to display the message:
To set the date of the weekly test, press CHANGE until the day on which you want to perform the test appears.
Press ENTER to confirm the date:
Press STEP to continue. The system displays the START TIME message. Follow the procedure under “Leak Test
Start Time” on page 8-7.
DAILY TEST
To run the tests daily, press CHANGE four times, then press ENTER in response to the ON DATE message:
The system displays the message:
Press STEP to continue. The system displays the START TIME message. Follow the procedure under “Leak Test
Start Time” on page 8-7.
AUTOMATIC TEST
NOTE: This option is available only if Line Leak Detector or Pump Sense is installed, configured and assigned to
the tank, or if External Input Type is configured as Pump Sense and assigned to the tank. (See section entitled
“External Input Type” on page 23-2.)
To run the tests automatically when Line Leak Detector or Pump Sense is installed, press CHANGE five times in
response to the ON DATE message:
TEST ALL TANK:
ON DATE
WEEKLY
PRESS <STEP> TO CONTINUE
TEST WEEKLY: ALL TANKS
MON
DAY
PRESS <STEP> TO CONTINUE
TEST ALL TANKS:
ON DATE
DAILY
PRESS <STEP> TO CONTINUE
TEST ALL TANK:
ON DATE