14
ATG Serial Port Setup
The ATG serial port settings must be configured to 9600 Baud, Data Bits 7, Parity Odd, Stop Bits 1. At the
console’s front keypad press the MODE key until the display reads
System Setup
in the display.
Press FUNCTION until you see the message:
Press STEP until you see the message:
This display allows you to access the communication settings—Baud Rate, Parity, Stop Bit and Data Length—for
any Comm board installed in the console’s Comm Bay.
Press ENTER to display the message:
The system labels the communications module in the leftmost slot as “COMM BOARD: 1”. If this is not the Comm
board to which you connected the Insite360 Connect, press TANK/SENSOR until the Insite360 Connect
connected Comm board displays.
The correct Baud Rate for Insite360 Connect is 9600. If the rate shown on the display is 9600, press STEP. If the
Baud Rate is incorrect, press CHANGE until you see the correct baud rate of 9600. Press ENTER to confirm
your choice. The system displays the message:
Press STEP to continue.
COMMUNICATIONS SETUP
PRESS <STEP> TO CONTINUE
PORT SETTINGS
PRESS <ENTER>
COMM BOARD: X (Type)
BAUD RATE: 1200
BAUD RATE: 9600
PRESS <STEP> TO CONTINUE
COMM BOARD: X (Type)
PARITY: ODD