Duct humidistat TDC-BH-U-W24 

 

 

Duct humidistat TDC-BH-U-W24 

 

 

Duct humidistat TDC-BH-U-W24 

 

Doc: 70-07-0114B-24, V1.4, 20160912 

© Vector Controls GmbH, Switzerland 

Subject to alterations 

TDC-BH-U Intelligent duct humidistat 

General description 

The TDC-BH-U is a stand-alone electronic binary humidity stat. The TDC-BH-U features one duct humidity 
sensor, one external NTC temperature sensor input and two binary outputs (Relays).  
A detailed parameterization is possible with the use of a simple configuration routine. The TDC-BH-U can be 
configured using the standard operation terminal. No special tools or software is required.  
Ordering, Name convention 
 

TDC-BH-U 

  │ ││ └───── 

Housing:  

U = Conduit connector, Blank: Cable gland 

  │ │└─────── 

Function 

H = Humidity 

  │ └──────── 

Output: 

B = Binary 

  └──────────

Series Indication 

TDC 

 

Item name 

Item code 

Variant 

Features 

TDC-BH-U-W20 
TDC-BH-U-W24 
TDC-BH-U-W25 

40-10 0059-20 
40-10 0059-24 
40-10 0059-25 

standard 
humidifying 
de-humidifying 

Binary controller with:  
1 Internal humidity input 
1 external temperature input (For set point 
shift) 
1 DO (Relay) for humidifier or dehumidifier 
1 DO (Relay) for fan (optional) 

TDC-BH-U-D-W20 
TDC-BH-U-D-W24 
TDC-BH-U-D-W25 

40-10 0060-20 
40-10 0060-24 
40-10 0060-25 

Deluxe 
humidifying 
de-humidifying 

Accessories

 

 

 

 

SOD-Tn10-1 
AES3-HT-A5 

40-20 0108 
40-50 0104 

Outdoor sensor 
Replacement humidity sensor 5% accuracy 

 

Selection of actuators and sensors 

External temperature sensors: Use only our approved NTC sensors to achieve maximum accuracy.  
Recommended is SDB-Tn10-15 as Duct sensor and SOA-Tn10 as outdoor sensor.  
Binary auxiliary devices: E.g. humidifiers, de-humidifiers and fans.  Do not directly connect devices that 
exceed 2(1.2) A. Observe startup current on inductive loads!  

Mounting location 

The Duct controller should be installed directly on the duct, in an area where the air stream is well mixed: 

 

Locate a supply air sensor two or three meters downstream from the nearest fan and coil. 

 

Mount the return air sensor close to the air inlet but downstream from a return fan if one is present. 

Installation 

1. 

Drill a hole with a diameter of 16 

mm (5/8”) in the air duct. 

2. 

Connect the wires to be connected to the terminals of the back part according to wiring 
diagram. 

3. 

Insert the probe in the hole; secure the back part to the duct with two 

–self-tapping screws.  

4. 

Connect the cable of the operating unit to the matching connector on the back part. 

5. 

Slide the two latches located on the left side of the front part into the hooks at the upper left 
side of the back part.  

6. 

Carefully lower the front part until the interconnector reaches the back part. Continue 
pressing in a gentle way until the front part is fully connected.  

7. 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure 
the front part to the back part. This screw is located on the front right side of the front part. 
There is no need to tighten the screw too much. 

Technical specification 

Important Notice! 

These controllers are for use as operation controls only and are not suitable for use as safety 

devices. Whenever a control failure could result in a loss of property or lead to personal injury, it is the responsibility 
of the installer, designer or user to incorporate additional safety devices to prevent such events. Tampering with the 
device or misapplication will void warranty. Observe switching currents on relays and local rules and regulations 

Power Supply 

Operating Voltage 

24 VAC ±10%, 50/60 Hz, Class 2, 48 VA max. 

 

Power Consumption 

Max. 1.5 VA 

 

Electrical Connection 

Terminal Connectors,  
wire 0.34…2.5 mm

2

 

(AWG 24…12)

 

 

Deluxe type only: 
Power backup for real time clock 

 
Min 48h if charged for 24h 

Signal Inputs 

Humidity Input:  
Range 
Accuracy 
 
Hysteresis 

Element: Polymer-Based Capacity Sensor 
0…100% r.H.  
10%...90% r.H. 

 5.0% 

0…10% and 90…100% 

 7.0% 

±1% r.H. 

 

Temperature Input 
Range 

External NTC (Sxx-Tn10 sensor):  
-

40…70°C (-40…158°F) 

 

Accuracy 

-

40…0°C (-40…32°F): 0.5 K 

0…50°C (32…122°F): 0.2 K 
50…70°C (122…158°F): 0.5 K 

Signal Outputs 

Digital Switching Outputs 

Switching type 
AC Switching power 

DO1…DO2 
Relays, Normally open 
2(1.2) A 

Environment 

Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0…50 °C (32…122 °F) 
<95 % r.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-

25…70 °C (-13…158 °F) 

<95 % r.H. non-condensing 
class 2M2 

Standards 

 

conform according to  
EMC Standard  
EMEI Standard 73/23/EEC  EN 61 000-6-1/ EN 61 000-6-3 

 

Product standards 

Automatic electrical controls 
for household and similar use 
Special requirement on 
temperature dependent 
controls 

 
EN 60 730 

–1 

 
EN 60 730 

– 2 - 9 

 

Degree of Protection 

IP52 to EN 60 529 

 

Safety Class 

III (IEC 60536) 

Housing 

Cover, back part 
Filter material 

Polycarbonate PC (UL94 class V-0) 
PTFE coated 1μm pores 

General 

Dimensions (H x W x D): 

Transmitter case: 
Probe: 

 
91 x 

68 x 47mm (3.7” x 2.7” x 1.9”) 

14 x 77 mm (

 

0.55 x 3”) 

 

Weight (including package) 

220g 

Power failure 

Upon power-interruption, all parameters and set points are memorized in non-volatile memory and therefore do not 
have to be re-entered again. 

Error messages 

Err1:

 

Humidity sensor faulty. The humidity sensor is damaged.  

Err2:

 

External input for temperature setback missing or damaged.  

Wiring diagram 

 

Terminal connections 

 

 

Dimensions mm (in) 

0V (GND) 

24V AC 

 

TDC-BH-U 

G0 

0…24V AC 

Q13 

7    8 

B1  M 

R

Q23 

Y

B1

 

Q14      

Y

B2

 

6  

Q24     

Description:  

1.  Connection for power-supply (24 V AC/DC, ±10%). In 

case of DC, connect the negative power-terminal. 
Common connection for analog in- and outputs.  

2.  Connection for power-supply (24 V AC/DC, ±10%). In 

case of DC, connect the positive power-terminal 

3. 

Normally open contact “DO 1” Humidify or Fan  

4. 

Normally open contact “DO 1” Humidify or Fan  

5. 

Normally open contact “DO 2” Dehumidify or Fan  

6. 

Normally open contact “DO 2” Dehumidify or Fan  

7. 

Thermistor input “RT” (Thermistor Sxx-Tn10) 

8. 

Thermistor input “RT” (Thermistor Sxx-Tn10) 

9. 

Observe maximum switching power of  

2(1.2)A per output! 

 

 
 

76 (3.0) 

47 (1.9) 

91 (3.6) 

6

8

 (2

.7