Temperature PI controller TCY- FT-U 

 

 

Temperature PI controller TCY- FT-U 

 

 

Temperature PI controller TCY- FT-U 

 

Doc: 70-00-0130C, V1.3, 20141030 

© Vector Controls GmbH, Switzerland 

Subject to alterations 

TCY-FT-U Intelligent Temperature PI controller 

Features 

 

Temperature PI control for HVAC systems.  

 

Up to 2 modulating outputs for DC 0...10V with 10mV resolution.  

 

1 internal temperature sensor and up to 2 external sensor inputs 

 

Multiple remote control functions on external input 

 

Password protected programmable user and control parameters 

 

Blue backlight 

Applications 

 

Various temperature control applications 

 

Stand alone VAV control for pressure independent actuators 

 

Water Only Systems: Radiator, floor heating or chilled ceilings 

 

Individual room control for offices, residential, hotel rooms, meeting rooms, etc.  

General Description 

The TCY-FT-U is a stand-alone electronic universal controller with one temperature control loop. It may use 
up to 2 PI sequences. The TCY-FT-U features 1 internal NTC temperature sensor, up to two external 
sensors inputs and up to four binary outputs. The configuration has been reduced to a minimum to allow for 
a simple and off the shelve usage. For more advanced features and current in- and outputs the TCI product 
range is recommended. The TCY-FT-U can be configured using the standard operation terminal. No special 
tool or software is required.  
 

TCY-FT2-U  

  │ │││ └──── 

Housing:  

U = Vertical (2” x 4”) housing, Standard is square housing 

  │ ││└────── 

Function:  

2 = 2-pipe, 4 = 4-pipe 

  │ │└─────── 

Input 

T = Temperature 

  │ └──────── 

Output: 

F = 3-point, M = Modulating, B = Binary 

  └────────── 

Series Indication 

TCY 

 

Item Name 

Item code 

Variant 

Features 

TCY-FT2-U-W1 

40-10 0068-1 

Cooling only 

Compact PI controller with: 
2 TI, 1 AO 

TCY-FT2-U-W2 

40-10 0068-2 

Heating only 

TCY-FT2-U 

40-10 0068 

2-Pipe system 

TCY-FT4-U 

40-10 0072 

4-Pipe system 

1 TI, 2 AO 

Accessories

 

 

 

 

S-Tn10-2 
SD-Tn10-12-2 
SD-Tn10-20-2 
SDB-Tn10-12 
SDB-Tn10-20 
SOA-Tn10 

40-20 0001 
40-20 0002 
40-20 0003 
40-20 0051 
40-20 0004 
40-20 0006 

Flying lead sensor with 2 m cable 
Flying lead duct sensor 12cm immersion depth, 2m cable 
Flying lead duct sensor 20cm immersion depth, 2m cable 
Duct sensor with housing, 12cm immersion depth 
Duct sensor with housing, 20cm immersion depth 
Outdoor sensor 

 

Selection of actuators and sensors 

Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-Tn10-20 as 
Duct sensor, SRA-Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.  

3-point Actuators:  

Actuators with constant running time are recommended. Observe power limits. Do not use actuators with 
power consumption > 6VA. Adjust running time in SW. Default running time is 90s for fully open / close 
running time.  

Mounting location 

 

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of 
average temperature. 

 

Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and 
heat emitting electrical equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and 
diffusers.  

 

Location of mounting is less critical if external temperature sensors are used 

Installation 

1. 

Connect the wires to be connected to the terminals of the power case according to wiring 
diagram 

2. 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front 
holding screw is facing to the ground. Make sure the mounting screw heads do not stand out 
more than 5 mm (0.2”) off the surface of the mounting plate.  

3. 

Ensure that the jumpers are set correctly.  

4. 

Slide the two latches located on the top of the front part into the hooks at the upper side of 
the mounting plate.  

5. 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue 
pressing in a gentle way until the front part is fully connected. While inserting the connectors, 
a slight resistance can be felt. This is normal. Do not use excessive force!  

6. 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure 
the front part to the mounting plate. This screw is located on the front lower side of the unit. 
There is no need to tighten the screw too much. 

 Display and Operation 

Power Failure 

Upon power-interruption, all parameters and setpoints are memorized in non-volatile memory and therefore do not 
have to be re-entered again. 

Error messages 

Err1:

 

The connection to the temperature sensor may be interrupted or the temperature sensor is damaged.  
The output is switched off. Verify parameter settings and wiring. 

Technical Specification 

Power Supply 

Operating Voltage 

24 V AC ± 10 %, 50…60 Hz, Class 2, 48VA max 

 

Power Consumption 

Max. 1.5 VA 

 

Electrical Connection 

Terminal Connectors,  
wire 

0.34…2.5 mm

2

 

(AWG 24…12)

 

Signal inputs 

Temperature Input 

 

 

Range 

0…50 °C (32…122 °F) 

 

Accuracy 

0.5 K 

Signal outputs 

TRIAC Outputs  
Switching power 

 
24 VAC, 250mA max 
Do not use actuators with power consumption > 
6VA 

Environment 

Operation 
Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0…50 °C (32…122 °F) 
<95 % r.H. non-condensing 

 

Transport & Storage 
Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25

…70 °C (-13…158 °F) 

<95 % r.H. non-condensing 
class 2MT2 

Standards 

conform according to  
EMC Directive 
2004/108/EU 
Low Voltage Directive 
2006/95/EU 

 
EN 61 000-6-1/ EN 61 000-6-3 

 

Product standards 
Automatic electrical controls for 
household and similar use 
Special requirement on temperature 
dependent controls 

 
EN 60 730 

–1 

 
EN 60 730 

– 2 – 9 

 

Degree of Protection 

IP30 to EN 60529 

 

Safety Class 

III (IEC 60536) 

Housing 

Cover, back part 
Mounting Plate 

Fire proof ABS plastic (UL94 class V-0) 
Galvanized Steel 

General 

Dimensions (H x W x D) 

Front part: 112 x 73 x 15 mm (4.4” x 2.9” x 0.6”) 
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”) 

 

Weight (including package) 

270 g (9.5 oz) 

 

 Wiring Diagram 

 

Description:  

G0 

0V 

 

Power supply:  

0VAC internally connected to signal common 

24V

  

Power supply:  

24VAC 

0V

  

Signal common:  

Common 0 potential for analog inputs and analog outputs. 

X1

 

RT  

External temperature input:  NTC 10k

Ω @ 25°C (77°F) 

 
TCY-FT2-U: 

 

X2

 

CO 

Change over input: 

NTC 10k

Ω @ 25°C (77°F) 

Y1

 

DO1  Binary output:  

Valve open 

Y2

 

DO2  Binary output:  

Valve close 

 
TCY-FT4-U: 
Y1

 

DO1  Binary output:  

Heating valve open 

Y2

 

DO2  Binary output:  

Heating valve close 

Y3

 

DO3  Binary output:  

Cooling valve open 

Y4

 

DO4  Binary output:  

Cooling valve close 

 

Dimensions [mm] (in) 

5

8

 (2

.3)

 

1

1

2

 (4

.4

73 (2.9) 

32 (1.2) 

15  

(0.6

0V (COM) 

24V AC 
 

TCY-FT2-U 

G0 

3    4   

Y1   Y2 

Y

F1

 

X

T CO 

  5       6 
 M       X2   

X

T EXT 

     7       8 
    M      X1 

0V (COM) 

24V AC 
 

TCY-FT4-U 

G0 

X

T EXT 

     7       8 
    M      X1 

3    4   

Y1   Y2 

Y

F1

 

5    6   

Y3   Y4 

Y

F2

 

Left (POWER): 

Press < 2 sec.: Toggle 

STANDBY-COMFORT mode or switch 
from OFF to ON 
Press > 2 sec.: Turn unit OFF. Text OFF 
displayed with current time (deluxe) 
temperature (standard) 
(Parameter setting: ENTER to select 
menu option, accept parameter change) 
 

Up : 

Increment SET POINT  

(Parameter setting: 
SCROLL menu options and 
parameters) 
 

Down : 

Decrement SET POINT  

(Parameter setting: SCROLL menu 
options and parameters) 
 

Mode 

Display of operation mode 

 
 

Large Digits: 

Display of input 

or parameter value. 

Indicators 

1 Remote temperature 

sensor 

2 Dew point sensor 

Vertical Bar: 

(scrolls 

up/down, 10% resolution) 

Small Digits: 

Display of 

setpoint, clock or parameter 
number. 
 

Right (OPTION) :  

Press < 2 sec.: Select Control Loop 
Press > 2 sec.: Manual H/C change 
(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 
 