background image

 

 

Contact Temperature Sensor SC-T 

 

 

Contact Temperature Sensor SC-T 

 

 

Contact Temperature Sensor SC-T 

 

Doc: 70-00-0215A, V1.0, 20140722 

© 2012-2014 Vector Controls GmbH, Switzerland 

Subject to alteration 

 

www.vectorcontrols.com

 

SC-T, Flying Lead Contact Temperature Sensor 

Features 

 

Thermistors and PT sensing elements to fit your system 

 

Strap-On mounting for pipes or arched surfaces 

 

Simple installation  

 

Wide range of temperature probes 

 

Including 2m (6.5ft) wire 

Applications 

 

Measure temperature for heating, ventilation and air conditioning 
applications 

 

For heating or cooling mode detection in 2-pipe systems 

 

As frost protection sensor 

Temperature sensor 

The sensor measures the temperature by use of a glass packed thermistor 
with a negative temperature coefficient (NTC), a platinum film (PT) or a nickel 

thin layer (NI) based probe. Its resistance changes according to the 
temperature. The change follows a specified curve. A summary of such curves 
is printed on the back of this document. Contact our sales department for 
curves or sensing elements not yet listed below.  

Compensating conductor resistance 

The length and type of conductors used to connect the sensor to the 

measuring electronic influences the accuracy of the measurement. Especially 
for elements with low resistance this has to be taken into account. 
Compensation needs to be performed by the measurement electronics.  

Ordering 

 

Item Name 

Probe 

Definition 

Cable length 

SC-Tn3-2 

NTC 3kΩ at 25°C (77°F) 

 B

25/50

 3935 

2m, (6.5ft) 

SC-Tn10-2 

NTC 10kΩ at 25°C (77°F) 

 B

25/50

 3935 

SC-Tn11-2 

NTC 10kΩ at 25°C (77°F) 

 B

25/50

 3630 

SC-Tn12-2 

NTC 10kΩ at 25°C (77°F) 

 B

25/50

 3380 

SC-Tn20-2 

NTC 20kΩ at 25°C (77°F) 

 B

25/50

 4200 

SC-Tn100-2 

NTC 100kΩ at 25°C (77°F) 

 B

25/50

 4200 

SC-Tp1-2 

PT100 

EN60751 

SC-Tp2-2 

PT1000 

EN60751 

SC-Tk5-2 

NI1000 

5000 ppm/K 

AMS-2 

Tightening strap for ½-3in pipes 

 

AMS-3 

Tightening strap for 3-6in pipes 

 

Technical Specification 

Warning!

 This device is intended to be used for comfort applications. Where a 

device failure endangers human life and/or property, it is the responsibility of the 
owner, designer and installer to add additional safety devices to prevent or detect 
a system failure caused by such a device failure. The manufacturer of this device 
cannot be held liable for any damage caused by such a failure.  
Failure to follow specifications and local regulations may endanger life, cause 

equipment damage and void warranty. 
 

Sensing Probe 

Thermistor: 
Range: (Probe only) 

Accuracy: 

 

  -40…0°C (-40…32°F):  

  0…50°C (32…122°F):  
  50…100°C (122…212°F):  
  > 100°C (> 212°F):  

NTC 
 -70…150°C (-94…302°F)  
 

0.5 K 
0.2 K 

0.5 K 
1 K 

 

Platinum-Film: 
Range: (Probe only) 
Accuracy 

PT according EN 60751 
-70…200°C (-94…392°F) 
EN 60751, Class B, ask for other class 

 

Nickel Thin Layer: 
Range: (Probe only) 

Accuracy 

1000 Ω at 0°C, 5000 ppm/K 
-60…200°C (-76…392°F) 

DIN 43760 

Cable 

Standard 

Size 
Insulation material 

Operating Temperature 
Ratings 

 

2 x 0.20 mm

2

 (AWG 24)

 

PVC 

 -40…80°C (-40…176°F) 
UL758, 1581/CSA C22.2 No 210.2 

 

High temperature 

Size 
Insulation material 
Operating temperature 

Ratings 

-H 

2 x 0.35 mm

2

 (AWG 22)

 

FEP 
-60...200°C (-76…392°F) 

ULR/CSA C22.2 No 210.2 

 

Plenum rated 
Size 

Insulation material 
Operating temperature 
Ratings 

-P 
2 x 0.5 mm

2

 (AWG 20)

 

Plenum PVC 
-20…75°C (-4…167°F) 
UL C(UL) PLENUM CMP OR E355847 

FPLP UL 

 

Single insulated PVC 
Size 

Insulation material 
Operating Temperature 
Ratings 

-A 
2 x 0.20 mm

2

 (AWG 24)

 

PVC 
 -40…80°C (-40…176°F) 
UL758,1581 CSA C22.2 No.210.2 

Environment 

Operation 
Climatic conditions 
Temperature depends on cable 

type 

To IEC 721-3-3 
class 3K5 
See above 

Transport & storage 
Climatic conditions 

Temperature 
Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3K3 and class 1K3 

-40…80°C (-40…176°F) 
< 95% RH non-condensing  

class 2M2 

Standards 

conform according to  
EMC Standard 89/336/EEC 
EMEI Standard 73/23/EEC 

 
EN 61 000-6-1/ EN 61 000-6-3 

 

Automatic electrical controls for 
household and similar use 
Special requirement on 

temperature dependent controls 

EN 60 730 –1 
 
EN 60 730 – 2 – 9 

 

Pollution Class 

Normal acc. to EN 60 730,  
RoHS compliant 

 

Degree of Protection 

IP65 to EN 60 529 

 

Safety Class 

III (IEC 60536) 

Housing 

Probe 

Brass 

 

Dimensions (Diameter x L) 

Probe: ø 6 x 35 mm (ø 0.25” x 1.4”) 

Contact Plate: 20x30mm (0.8” x 1.2”) 

 

Weight (including package) 

80g (2.8oz) 

Wiring & Installation 

Wiring Diagram 

 

Dimensions 

[mm](in) 

 

Installation 

Mount the sensor on a supply or return pipe depending on application.  
Make sure the maximum allowed temperature limit is not exceeded.  
For better temperature transfer between sensor and medium use heat 
conducting paste or heat conducting pads.  

If possible place the sensor on the upper side of the pipe to prevent 
permeation by condensate.  
Bend the wings of the contact sensor to fit to the radius of the pipe.  
Place the heat conducting pad or liquid between pipe and sensor and use the 

tightening strap to fix the sensor to the pipe. Use moderate torque, do not 
crush the sensor.  

 

 

SC-Tn10-2A 

 

 

Cable type: 

 

default: PVC cable double insulated 

 

-H = High temperature 

 

-P = Plenum rated 

 

-A = PVC cable single insulated 

 

Cable length in Meter 

 

Sensing Element (see below) 

 

Sensor Type: Sensor with flying lead 

20 

(0.8) 

35 (1.4) 

3

0

 (

1

.2

 6 (0.2) 

 
 

 

 

SC-T 

RT 

Reviews: