ACR35

Maintenance

Since fan motors and other components are maintenance 

free, no maintenance other than cleaning is necessary. 

The level of cleaning can vary depending on local condi-

tions. Undertake cleaning at least twice a year. Inlet and 

exhaust grilles, impeller and elements can be vacuum 

cleaned or wiped using a damp cloth. Use a brush when 

vacuuming to prevent damaging sensitive parts. Avoid 

the use of strong alkaline or acidic cleaning agents.

Overheating

The air curtain unit with electric heater is equipped with 

an overheat protector. If it is deployed due to overhea-

ting, reset as follows:

1.   Disconnect the electricity with the fully 

  isolated switch.

2.  Allow the electrical coil to cool.

3.  Determine the cause of overheating and rectify 

  the fault.

Reset is performed as follows:

1.   Locate the red button inside the air curtain unit. 

  It is visible and accessible by opening of the service 

  hatch and inlet grille. The button is on the left side 

  seen from inside the room looking out. On the 

  2 metre variant, two red buttons are installed in the 

  middle of the unit. 

2.  Press the red button until a click is heard.

3.  Connect the air curtain again. 

All motors are equipped with an integral thermal safety 

cut-out. This will operate, stopping the air curtain 

should the motor temperature rise too high. The cut-out 

will automatically reset when the motor temperature has 

returned to within the motor's operating limits.

Temperature control

Temperature control of PLS maintains the exhaust 

temperature at +40 °C.  If the temperature should exceed 

anyway there is an overheating alarm. For more infor-

mation see the manual for PLS.

 

Fan replacement 

1.   Determine which of the fans is not functioning.

2.  Disconnect the cables to the relevant fan.

3.  Remove the screws securing the fan and lift the fan 

 out.

4.  Install the new fan as above in reverse order.

Replacing the electric heater/coil (ACR35-E)

1.   Mark and disconnect the cables to the electric 

 heater/coil.

2.  Remove the mounting screws securing the electric  

  heater/coil in the unit and lift the electric heater/coil 

 out.

3.  Install the new electric heater/coil in reverse order 

  to the above.

Replacing the water coil (ACR35-W)

1.   Shut off the water supply to the unit.

2.  Disconnect the connections to the water coil.

3.  Remove the mounting screws securing the coil in the 

  unit and lift the coil out.

4.  Install the new coil in reverse order to the above.

Draining the water coil (ACR35-W)

The drain valve is on the underside of the coil on the 

connector side. It can be accessed via the service hatch.

Summary of Contents for ACR35

Page 1: ...ACR35 Art nr 172787 01 GB Installation and maintenance instruction for air curtains IMPORTANT Read these instructions before the product is installed and used Save the instructions for future use 2 ...

Page 2: ...unting and operating instructions Application area The Thermo zone ACR35 air curtain unit is supplied with electrical heating or hot water coil and is intended for installation above entrances and smaller doors up to 3 5 metres in height ACR35 is recessed in false ceilings above entrances Protection class above false ceiling IP44 below false ceiling IP20 Operation Air is drawn in from underneath a...

Page 3: ...to a closed water heating sys tem The heating coil must not be connected to a mains pressure water system or an open water system Note that the unit shall be preceded by a regulating valve see VEAB valve kit To access the connections DN20 3 4 outside thread the service hatch and intake grille must be opened The water coil is connected inside the unit through holes which are made during installatio...

Page 4: ...e equipped with an integral thermal safety cut out This will operate stopping the air curtain should the motor temperature rise too high The cut out will automatically reset when the motor temperature has returned to within the motor s operating limits Temperature control Temperature control of PLS maintains the exhaust temperature at 40 C If the temperature should exceed anyway there is an overhe...

Page 5: ...ing That the water coil is air free That there is enough water flow That incoming water is heated enough If the fault cannot be rectified please contact a qualified service technician Residual current circuit breaker applies to units with electric heater When the installation is protected by means of a residual current circuit breaker which trips when the appliance is connected this may be due to ...

Page 6: ...6 ACR35 A 302 B C 638 523 595 325 532 D Mounting Fig 1 The mounting brackets on delivery Type A mm B mm C mm ACR35 10 1057 1016 1067 ACR35 15 1567 1526 1577 ACR35 20 2073 2031 2083 ...

Page 7: ...7 ACR35 Fig 2a Mounting on threaded bars Mounting Fig 2b Mounting on threaded bars inside unit ...

Page 8: ... AR Service hatch Fig 5 PLS inside unit Water connections Fig 4 The water coil is connected inside the unit through holes which are made during installation on the upper side or through the side of the unit possible places are marked with punch marks ...

Page 9: ...ee way valve and actuator on off 230 V DN15 VOT20 Three way valve and actuator on off 230 V DN20 VOT25 Three way valve and actuator on off 230 V DN25 VAT Adjustment tool for valve kit VOS 230 V Control valves for water systems optional PLSB Control unit Basic Incl control unit PLSUB1 and 5 meter modular cable with RJ12 quick connect IP30 PLSAC Control unit Competent Incl PLSUA1 control unit box co...

Page 10: ...10 ACR35 Transformer 230V 200V 170V 145V 120V 100V N Blue Black AR3520A W AR3515A W SIReB1 AR3510A W Wiring diagrams ACR35 Internal wiring diagram ACR35 W ...

Page 11: ...1 L2 L N L3 Black Grey Blue Transformer 230V 200V 170V 145V 120V 100V N Blue Black AR3520E18 AR3515E14 SIReB1 AR3510E09 400V3 230V AR3510E09 3515E14 AR3520E18 Wiring diagrams ACR35 Internal wiring diagram ACR35 E ...

Page 12: ... optional PLSUB1 230V Wiring diagrams Electric Basic Basic parallell X5 C2 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V PLSB1 PLSRTX optional PLSUB1 X5 C2 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V PLSB1 230V 230V Wiring diagrams for PLSAC Competent see manuals for PLS ...

Page 13: ...ional PLSUB1 X5 C2 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V PLSB1 SD230 X5 C2 X4 C1 X3 ROOM PE N L SUPPLY 230V ACTUATOR 230V PLSB1 SD230 Basic parallell Wiring diagrams for PLSAC Competent see manuals for PLS C PLSB2 SD230 PLSRTX optional PLSUB1 C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY ...

Page 14: ...tt 556138 3166 VAT no SE556138316601 Postal Cheque Service 48 51 08 5 Bank Transfer 926 0365 Fax Int 46 451 410 80 E mail veab veab com Phone Int 46 451 485 00 Website www veab com NB We reserve us from typographical errors and the right to make changes and improvements to the contents of this manual without prior notice ACR35 14 ...

Reviews: