11.2.7 Checking the current sensor values
Select the
System
page.
Check the current sensor values I Grid1, I Grid 2 and I
Grid 3 for plausibility:
If a current sensor value is approx. 0, although this phase
is currently loaded, the connection between current
sensor and battery storage system may be erroneously.
If necessary, load all phases separately: Switch on
selected consumers or manually discharge the battery
storage system. See chapter 9.4.3.
Note:
During a manual discharge, current from the
battery storage system is systematically applied to the
phases.
Check the current flow through all three phases, using the
current probe if necessary!
Procedures in case of unusual current sensor values: