42
Subject to alteration!
Updated 11/2015
Adequate rodent protection must be provided.
The substrate, connecting walls and ceiling must not be
made of heat-sensitive material.
The installation location must conform to a pollution index
of 2.
Access to the shut-down functions must be guaranteed.
The
On/Off
key must not be blocked.
Smoking is prohibited at the installation location.
8.1.2
Installation location and the surrounding area
The cabinet must not be installed in the following locations:
at which temperatures may reach freezing point, such as
garages, carports or other locations
at which air humidity can exceed 80 % and condensation
can penetrate the saline moisture
flood areas
earthquake zones
– additional safety procedures are
required in such areas
that contain ammonia
at heights of over 2000 meters
potentially-explosive atmospheres
exposed to direct sunlight
that undergo major ambient temperature fluctuations
wet areas (environment category 2)