14
Värmebaronen MP4 G2 / MP6 G2
Menu - Advanced Service Level
Delivery setting
area
std
20.
0
Upper temperature function, choice of method.
Absolute value for upper temperature.
0 = absolute
1
20.
1
Temperature relative to setpoint.
1 = relative
21. 10
Temperature level of the upper temperature function - setting
This parameter is used regardless of the above selection.
To be adjusted if an absolute value is selected for the upper temperature.
6 – 105°C
15°C
22.
0
Frost protection - the choice of whether frost protection should be active or inactive.
Frost protection inactive.
0 = off
1
22.
1
Frost protection active.
1 = on
23.
0
Manual tests
Manual tests according to rows 24 - 26, disabled
0 = off
0
23.
1
Manual tests according to rows 24 - 26, are possible.
The function is deactivated automatically after 4 minutes.
1 = on for 4
min
24
0
Power connection.
Connection can only be done after the function is activated in row 23.
0, 1 and 2
0
24
1
Press + or - to select number of power stages.
Manual connection is subordinate to all protection functions.
25.
0
Circulation pump
Connection can only be done after the function has been activated in row 23.
0 = off
0
25.
1
Manual connection of the circulation pump.
Press + or - to select.
1 = on
26.
0
Buzzer alarm.
Connection can only be done after the function is activated in row 23.
0 = off
0
26.
1
Manual connection of buzzer alarm.
Press + or - to select.
1 = on
27. 30
Display of the temperature of the power circuit board.
Temperature too high >55° C.
0 – 55°C
28. --
Room unit and UTK function not selected.
28. 30
UTK room unit, P-factor, proportional impact, 0.1°C/°C.
Adjustment should only be performed by a person with an understanding
of the impact!
0 – 100
30
29. --
Room unit and UTK function not selected.
29. 10
UTK room unit. I-factor, I-part impact, 0.1°C/°C/h.
Adjustment should only be performed by a person with an understanding
of the impact!
0 – 100
10
Enter 21 in the menu "Service level" row 19, for access to menu "Advanced Service Level"!
Advanced Service Level, rows 20-29, alternate between row number window and parameter value.