WARNING
The incorrect setting of the FOC dynamic may cause:
• Speed oscillations if the FOC dynamic is too slow.
• Overcurrent or igbt trip alarms if the FOC dynamic is too fast.
It is recommended to intervene promptly by appropriately adjusting the "FOC Dynamic"
parameter if the conditions listed above are present. Lack of intervention could lead to
damage to the inverter, the motor and the system.
9.5. Menu
Access to the menus is password-protected at two levels:
•
Installer level
: Allows the modification of parameters related to the operation of the pump in the hy-
draulic system on which it is installed.
Password 1, default 001.
•
Advanced level
. It allows for the modification of parameters so critical that, in case of the wrong set-
ting, they may compromise the life of the device, the pump, and the system.
Password 2, default
002.
Within each menu, it is possible to change the relative access password.
NOTE
Access to the installer or advanced level by means of an incorrect password entails only
the possibility of displaying the parameters set without any possibility of modification.
In case of loss of the password, it is advisable to contact technical support to obtain the
universal password.
Menu
Description
Level
Default
password
Control. param.
Menu of parameters relating to the control of the pump in the
hydraulic system in which it is installed.
Installer
001
Motor parameters
Motor control parameters menu
Advanced
002
IN/OUT paramet.
Parameter menu for analogue and digital inputs and outputs
Installer
001
Connect. param.
Parameters menu for connectivity and external communica-
tion.
Installer
001
PSDrive
36