WPIR-EXT
Installation Instructions/User Manual
4
Edition Date: 26.07.2021
Doc ID: I-200478
3. Operation
This WPIR-EXT detector transmits the following events data:
•
SUPERVISION
– A periodical transmission (configurable) indicating detector’s presence.
•
ALARM
– Alarm transmission triggered by the device indicating Motion detection. The Red LED will blink once.
•
LOW BAT
– Whenever the battery reaches the low level (2.5V), a Battery Low signal will be sent. When Battery
level drops below Cut Off level (2.3V) the device will stop functioning and the Red LED will blink for 10 seconds
and then turned Off.
•
TAMPER
– Whenever the cover is removed from Bracket or the device is tear off from the wall, a message will
be transmitted with “Tamper ON” signal. When cover will be returned a “Tamper OFF” signal will be transmitted.
•
ANTI-MASKING
– If an attempt is made to mask the lens with a sticker or to put a masking object close to the
lens, a trouble alert will result up to 180 seconds after masking. A mask signal is also reported on your SPC
system.