16.6.4.3 Edit Keypads
To edit keypads:
1. Scroll to KEYPADS > EDIT.
2. Press SELECT.
3. Scroll to the device to be edited and press SELECT.
The configuration settings for a standard keypad and comfort keypad are described in the
sections below.
4. Press BACK to exit the menu.
LCD Keypad Settings
Configure the following settings for the keypad.
Setting
Description
Description
Enter a unique description to identify the keypad.
Function Keys (in idle state)
Panic
Select Enable, Disable or Enabled Silent. If enabled, panic alarm is activated by pressing the 2
soft keys together.
Verification
If you assign a verification zone to the keypad, when a panic alarm is triggered by pressing 2 soft
keys together or by entering a duress code, audio and video events are activated.
Visual Indications
Backlight
Select when keypad backlight is on. Options are: On after key is pressed; Always on; Always off.
Indicators
Enable or disable the LED’s on the keypad.
Setting
state
Select if setting state should be indicated in idle mode.
Audible Indications
Buzzer
Enable or disable the buzzer on the keypad.
Partset
Buzzer
Enable or disable buzzer during exit time on Partset.
Keypress
Select if the speaker volume for the key presses should be activated.
Deactivation
Calendar
Select if the keypad should be limited by calendar. See
Mapping
gate
Select if keypad should be limited by a mapping gate.
Keyswitch
Select if keypad should be limited by a keyswitch.
PACE
Entry
Tick this box to disable the keys on the keypad during the entry time when a PACE is configured
on the keypad.
Areas
Location
Select the secured area where the keypad is located.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the keypad
© Vanderbilt 2018
126
A6V10276959-d