Label
Description
Label
Description
C
Door networks
H
Important:
Place varistor across all lock terminals.
Note:
Diagram shows normally energised Magnetic
Lock.
D
Controller network
J
Break glass unit (double pole)
E
Break glass monitoring, normally
closed
3.2 Wiring exit readers
For clock and data readers, wire exit readers in parallel but leave the sense line unconnected.
For Wiegand readers, wire the DATA 0 of the exit reader to SENSE on the ACTpro-1500.
Max length: 100m with 12V DC
Cable: 8 core screened Belden 9504 or equivalent
3.3 Adding the OSDP EOL Jumper for OSDP Readers
When attaching OSDP readers to the ACTpro-1500 family of controllers, ensure that the EOL jumper is on
the last two pins (EOL position) on the last reader only.
Jumper location on ACTpro-1500 PCB
Jumper position for standard operation
Jumper position for OSDP operation
You cannot network ACTpro-1500 controllers when OSDP readers are attached.
3.4 Fire override configuration
To release doors on fire alarm activation:
1. In ACT Manage, configure a door group called
Fire Doors
that contains all fire doors, then select
that group from the
Settings > Doors > Fire Override Doors
drop-down list.
ACTpro-1500/-15002A/-1500PoE Door Controller – Installation and Operating Instructions
Wiring
© Vanderbilt 2019
12
A-100535-c