Note:
Batteries must have sufficient charge to supply the load.
6. Reconnect mains power.
Green LED should be on.
7. Remove Load fuse and check that the red Fault LED is on (dependent on model).
2.2.5 Tamper
A tamper condition is reported in software.
1. Check that the tamper switch is:
l
Closed when the enclosure is mounted on the wall, lid is closed, and the lid screw is fitted.
l
Open when the lid is open.
2. Close cover and secure using fastening screw(s) provided.
2.3 ACT365-ACUPoE
This unit must be fed from a compliant PoE (power over Ethernet) power source (PoE 802.3bt for 3A
power output).
2.3.1 Mounting
1. Mount the boxed module securely using the enclosure mounting points in the correct orientation,
allowing 100mm clearance around the enclosure – see diagram.
2. Route cables via knockouts and/or rear cable enclosure entry holes.
2.3.2 Power Up
1. Attach correctly rated load cable to load equipment and fasten using cable ties.
Note polarity.
2. Attach suitable Ethernet cable from PoE++ source to POE IN RJ45 connector (100m max from
PSE).
3. Attach suitable Ethernet cable between IP device and DATA RJ45 connector (if required).
4. Connect charged 12V battery 7Ah to the other end of battery cable.
Note:
Ensure correct polarity of battery connections: + use Red lead, - use Black lead.