4.3 Defaulting the static IP address
The static IP address can be reset to the default value of 192.168.1.60.
1. Power down the ACT365-ACU Controller.
Ensure nothing is connected to the tamper input terminal and the tamper spring is
not pressed, otherwise the following steps will factory default the controller losing
all information.
2. Set the DHCP DIP switch 1 to
OFF
.
3. Set the DEFAULT DIP switch 2 to
ON
.
4. Re-apply power.
5. Wait approximately 5 seconds, until the controller confirms default completed by sounding the
buzzer.
6. Remove power.
7. Set the DEFAULT DIP switch 2 to
OFF
.
8. Re-apply power.
Note:
The static IP address can be changed via the web interface.
4.4 Changing static IP address on the ACT365-ACU
1. Connect the ACT365-ACU Controller to the IP network.
2. Open a web browser on a PC (for example, Microsoft Internet Explorer, Google Chrome, etc.).
3. Enter http://<NetBIOS address>, e.g. http://ACT365ACU010049
4. Logon details:
Username:
installer
Password:
999999
5. Choose the
Communication
menu and set the
following:
l
Static IP Address
l
Network Mask
l
Default Gateway
6. Click
Save IP Settings
.
Note:
Use the new IP address when connecting to the
controller.
ACT365-ACU / ACT365-ACU2A / ACT365-ACUPoE – Installation Instructions
Defaulting the Controller and IP Address
Configuration