AIR N ARC 300
®
ALL-IN-ONE POWER SYSTEM
®
APPENDIX A: ADDITIONAL INFORMATION
090010-OP_r0
PAGE - 157
APPENDIX A:
ADDITIONAL INFORMATION
A.1 ELECTRIC MOTOR CHART - STARTING WATTS
I
HORSEPOWER
RUNNING
WATTS
UNIVERSAL
MOTOR
(sm. appliance)
INDUCTION
MOTOR
CAPACITOR
MOTOR
SPLIT
PHASE
MOTOR
1/6
275
400
600
850
1200
1/4
400
500
850
1050
1700
1/3
450
600
950
1350
1950
1/2
600
750
1300
1800
2600
3/4
850
1000
1900
2600
X
1
1000
1250
2300
3000
X
1 1/2
1600
1750
3200
4200
X
2
2000
2350
3900
5100
X
3
3000
X
5200
6800
X
5
4800
X
7500
9800
X
I
Approximate current requirements.
NOTE
For pumps, air compressors, air
conditioners, inverters add at least 25%
to starting current.