9.2 Tests and environmental
conditions
9 Technical data
Technical description
196
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
9.2.4.
Environmental conditions
Test
Standard & Test class / level
Test value
Device in operation
- Dry heat
EN / IEC 60068-2-2, Bd
+65°C
- Cold
EN / IEC 60068-2-1, Ad
-40°C
- Damp heat, cyclic
EN / IEC 60068-2-30, Db
From +25°C to +40°C,
From 93% RH to 98% RH,
6 days
-
Damp heat, static
EN / IEC 60068-2-78, Cab
+40°C, 93% RH, 10 days
- Flowing mixed gas
corrosion test, method 2
IEC 60068-2-60, Ke
+25°C, 75% RH,
10 ppb
, 200 ppb
,
10 ppb
- Flowing mixed gas
corrosion test, method 4
IEC 60068-2-60, Ke
+25°C, 75% RH,
10 ppb
, 200 ppb
,
10 ppb
, 200 ppb
Device in storage
- Dry heat
EN / IEC 60068-2-2, Bb
+75°C
- Cold
EN / IEC 60068-2-1, Ad
-40°C
9.2.5.
Casing
Degree of protection (IEC 60529)
IP54
Dimensions (W x H x D)
130 x 170 x 210 mm
Material
1 mm steel plate
Weight
2.0 kg
Colour code
RAL 7032 (Casing) / RAL 7035 (Back plate)
9.2.6.
Package
Dimensions (W x H x D)
320 x 215 x 175 mm
Weight (Terminal, Package and Manual)
3.0 kg