Valworx 5818 Series Installation Instructions Manual Download Page 1

   

  

 

Doc: iom5818eps.0322                                                                   Cornelius, N.C.  •  USA               

                                                          www.valworx.com 

 
IOM 

5818 
EPS 

Installation Instructions 

Electric Actuators with EPS Positioner

 Explosion 

Proof 

5818 Series

 

APPLICABLE STANDARDS                                                                                           

ANTI EXPLOSION GRADE 

The anti-explosion grade of these actuators is  

 

Class 1, Division 1, Groups C & D T5 

 

Ex db IIC T5 Gb Class 1 Zone 1 

 

AEx db IIC T5 Gb 

Where: 

Class I 

 Hazard Class 

Division  I/ Zone 1 

 Area Classification 

db 

 Explosion Proof Type 

II 

 Electrical Equipment design for explosive atmospheres (except colliery) 

 Magnitude of the explosion 

T5 - Highest allowed surface temperature of the actuator (+55C) 
Gb 

 Protection Grade 

 
The grades of combustible gas, steam and temperature group are listed in 
CSA 22.2 No 60079-0-2019, CSA 22.2 No 60079-1-2016, CSA 22.2 No 
30-M1986(R2016), CSA 22.2 No 145-11(R2015), ANSI/UL 60079-2:2020, 
ANSI/UL 1203-

2013, ANSI/UL 674 Fifth Edition. It is the user’s responsibility 

to ensure compatibility with the applicable regulations.

 

Models: 581856, 581857, 581876, 581877 

READ  THESE  INSTRUCTIONS  CAREFULLY  BEFORE  INSTALLING  OR  CONNECTING 
POWER  TO  THE  ACTUATOR.  THE  ACTUATOR  MUST  BE  INSTALLED,  COMMIS-
SIONED,  OPERATED  AND  REPAIRED  BY  QUALIFIED    PERSONNEL.  COMPLY  WITH 
ALL APPLICABLE CODES, STANDARDS AND SAFETY REGULATIONS.  

INTRODUCTION  

This  document  provides  installation,  operation  and  maintenance  instructions  for  
Valworx  5818  series  electric  actuators  with  EPS  Postitioner.  These  actuators  are 
typically  used  to  operate  quarter-turn  valves.  Every  actuator  has  been  fully  tested 
prior to shipment to ensure trouble free operation.

 

CONDITIONS FOR USE 

Failure to follow any of these conditions and warnings may void the warranty.     
Valworx expressly disclaims any and all damages including consequential damages 
resulting therefrom. 

1.  If the entry point, connecting pipe or contained cable exceeds 60°C the user 

shall select the appropriately rated cable, cable gland and/or conductors in the 
conduit and shall install per the IOM. 

2.  The minimum yield strength and minimum tensile strength of the explosion proof 

conduit connector are 450MPa and 700MPa respectively. 

3.  The rated load is 50Nm (58185X series) and 200Nm (58187X series). Do not 

exceed the rated load. 

4.  The lens plate shall not be loosened or removed at any time. 

5.  This unit contains the adhesives TSE3854DS-W and WCC-87 and cannot be used 

in an atmosphere containing the following saturated vapors: Acetic Acid (glacial), 
Acetone, Ammonium Hydroxide (20% by weight), ASTM reference fuel C,    
Diethyl Ether, Ethyl Acetate, Ethylene Dichloride, Furfural, n-Hexane, Methyl Ethyl 
Ketone, Methanol, 2-Nitropropane, and Toluene. 

6.  This explosion proof actuator is rated for T5. Ambient temperatures shall not 

exceed -25°C ~ +55°C (-13°F ~ 131°F). 

    WARNING 

1.  To prevent the ignition of flammable gases, do not remove the cover while cir-

cuits are energized.                                                                                       

-avertissement

 

pour éviter l’inflammation des gaz inflammables, de vapeurs our 

de poussiére, ne pas retirer le couvercle pendant que le circuit est sous tension

 

2.  Explosion-proof sealing material shall be used to seal the explosion proof connect-

ing pipe, and the distance from the seal to the actuator shall not exceed 500mm. 

-avertissement

 un scellement doit étre installé a moins de 500 mm du boítier

 

3.  The lens plate shall not be loosened or removed at any time. 

4.  The cable entry and connecting conduit shall not exceed 66°C(150.8°F) & 

77°C(170.6°F) respectively.  

5.  Do not damage or otherwise make the nameplate illegible. 

6.  Avoid damaging or scratching the flameproof joints when servicing or installing 

the actuator. Ensure the fastening screws connecting electric elements, junction 
box cover, and motor box cover are appropriately tightened. 

7.  The electric motor cavity of this product is an independent explosion proof cavity.   

Do not remove the motor cover or faying surface of the outlet lead. 

8.  This product must be grounded internally and externally. Ensure ground connec-

tions are secure and check regularly.                                                                

9.  Wiring connections shall comply with applicable codes and standards. Connecting 

cables shall have an explosion proof rating of at least Exdb IIC T5 Gb.                 

 

 

 

CAN/CSA C22.2 No.30-M1986 
(Reaffirmed 2016) 

CAN/CSA C22.2 No. 145-11 
(Reaffirmed 2015) 

 

CSA C22.2 No. 139-13 

CSA C22.2 No.60079-0-2019             

 

CSA C22.2 No.60079-1-2016 

 

 

 

 

UL 674 Fifth Edition 

 

 

UL 1203-2013 

 

UL60079-0:2020 

                                                 
UL 60079-1:2020 

 

UL 429 (Seventh Edition) 

 

Explosion proof enclosures for use in 
class I hazardous locations                   

Electric Motor and Generators for 
Use in Hazardous (Classified)     
locations 

Electrically Operated Valves 

Explosive atmospheres-Part 0: Equip-
ment-General requirements  

                                               
Explosive atmospheres-Part 1: Equip-
ment protection by flameproof en-

closure “d” 

 

Electric Motors and Generators for 
Use in Hazardous (Classified) Loca-
tions                                                    

Explosion Proof and Dust Ignition 
Proof Electrical Equipment for Use in 
Hazardous (Classified) Locations 

Explosive atmospheres-Part 0: Equip-
ment-General requirements  

Explosive atmospheres-Part 1: Equip-
ment protection by flameproof en-

closure “d” 

 

Electrically Operated Valves 