9.2.2
Address of Stop Command
In that box you can modified the condition to stop the sequence. The stop command has priority
on the start command
Address:
Address of the PLC digital input.
Delay:
Delay that the condition needs to be true to
stop the sequence.
Type:
Normally open or normally closed contact.
Equipment
: Programmed level sensor.
Start by Level %:
level setpoint.
HIGH/LOW:
The actual level must be higher than the setpoint.
The actual level must be lower than the setpoint.
9.2.3
Interlock
Stop a sequence or prevent it from starting if another sequence is started
Select the sequences that will have priority on the sequence
you are programming. If two sequences have the interlock
enable between each other, the first to start have priority.